Datasheet

II-2016, www.findernet.com
E
Electronic voltage monitoring relays for
three-phase applications
Multifunctional types, providing the flexibility
of monitoring Undervoltage, Overvoltage,
Window Mode, Phase rotation, Phase loss,
Asymmetry and Neutral loss
Phase loss monitoring, even under phase
regeneration
Positive safety logic - Make output contact
opens if the relay detects an error
All functions and values can be easily adjusted
by the selector and trimmer on front face
“Blade + cross” – both flat blade and cross
head screw drivers can be used to adjust the
regulators and the function selector
Colored LEDs for clear & immediate visual
indication
1 or 2 CO relay output, 6 or 8A
Modular housing, 35mm wide
35mm rail (EN60715) mount
Cd-free contact material
Screw terminal
70.41 70.42
Three-phase (380…415V, with
or without neutral) voltage
monitoring:
Window mode (overvoltage +
undervoltage)
Phase loss
Phase rotation
Asymmetry
Neutral loss selectable
Three-phase (380…415V,
with neutral) voltage
monitoring:
Undervoltage
Overvoltage
Window mode (overvoltage +
undervoltage)
Voltage fault memory
selectable
Phase loss
Phase rotation
Asymmetry
Neutral loss
For outline drawing see page 10
Contact specification
Contact configuration 1 CO (SPDT) 2 CO (DPDT)
Rated current/Maximum peak current A 6/10 8/15
Rated voltage/
Max. switching voltage VAC 250/400 250/400
Rated load AC1 VA 1500 2000
Rated load AC15 VA 500 400
Single phase motor rating (230VAC) kW 0.185 0.3
Breaking capacity DC1: 30/110/220V A 6/0.2/0.12 8/0.3/0.12
Minimum switching load mW (V/mA) 500 (12/10) 300 (5/5)
Standard contact material AgNi AgNi
Supply specification
Nominal system voltage (U
N
) VAC (50/60Hz) 380…415 380…415
Rated power VA (50Hz)/W 11/0.9 12.5/1
Operating range VAC (50/60Hz) 220…510 220…510
Technical data
Electrical life at rated load AC1 cycles 60·10
3
60·10
3
Voltage detection level range V 300…480 300…480
Asymmetry detection level range % 4…25 5…25
Switch-off delay time (T on function diagrams) s 0.5…60 0.5…60
Switch-on lock-out time s 1 1
Switch-on hysteresis (H on function diagrams) V 10 (L-L) 10 (L-L)
Power-on activation time s ≈ 1 ≈ 1
Insulation between supply
and contacts (1.2/50µs) kV 4 4
Dielectric strength
between open contacts VAC 1000 1000
Ambient temperature °C –20…+60 –20…+60
Protection category IP 20 IP 20
Approvals (according to type)
2
70 SERIES
Line monitoring relay
70
SERIES