Datasheet

II-2016, www.findernet.com
E
Electronic phase loss and rotation monitoring
relays for three-phase applications
Universal voltage monitoring (U
N
from 208V to
480V, 50/60Hz)
Phase loss monitoring, even under phase
regeneration
Positive safety logic - Make contact opens if the
relay detects an error
2 versions:
1 CO relay output, 6A (17.5mm wide), and
2 CO relay output, 8A (22.5mm wide)
35mm rail (EN60715) mount
European patent pending for the innovative
principle at the root of the 3 phase monitoring
and error survey system (70.61)
Screw terminal
70.61 70.62
Three-phase (208…480)V
voltage monitoring:
Phase loss
Phase rotation
Three-phase (208…480)V
voltage monitoring:
Phase loss
Phase rotation
For outline drawing see page 10
Contact specification
Contact configuration 1 CO (SPDT) 2 CO (DPDT)
Rated current/Maximum peak current A 6/15 8/15
Rated voltage/
Max. switching voltage VAC 250/400 250/400
Rated load AC1 VA 1500 2000
Rated load AC15 VA 250 400
Single phase motor rating (230VAC) kW 0.185 0.3
Breaking capacity DC1: 30/110/220V A 3/0.35/0.2 8/0.3/0.12
Minimum switching load mW (V/mA) 500 (10/5) 300 (5/5)
Standard contact material AgCdO AgNi
Supply specification
Nominal system voltage (U
N
) VAC (50/60Hz) 208…480 208…480
Rated power VA (50Hz)/W 8/1 11/0.8
Operating range VAC (50/60Hz) 170…500 170…520
Technical data
Electrical life at rated load AC1 cycles 100·10
3
60·10
3
Switch-off delay time s 0.5 0.5
Switch-on lock-out time s 0.5 0.5
Power-on activation time s <2 <2
Insulation between supply
and contacts (1.2/50µs) kV 5 5
Dielectric strength
between open contacts VAC 1000 1000
Ambient temperature °C –20…+60 –20…+60
Protection category IP 20 IP 20
Approvals (according to type)
3
70
SERIES
70 SERIES
Line monitoring relay