Datasheet

X-2013, www.findernet.com
5
G
7F
SERIES
7F SERIES
Filter Fan (24…630)m
3
/h
Filter Fan for electrical cabinets and
enclosures 24VDC versions
Very low acoustic noise
Minimal depth within enclosure
Air volume (14…470)m
3
/h
with Exhaust Filter installed in cabinet)
Air volume (24…630)m
3
/h (free flow)
Power consumption (4…130)W
Operating voltage: 24VDC
Time-saving installation and maintenance
Further available versions*:
- EMC Filter Fan (7F.70) and
EMC Exhaust Filter (7F.07)
- Filter Fan supplied in Reverse flow mode
(7F.80)
* Product codes, see pages 6 & 9
7F.50.9.024.3100 7F.50.9.024.4230
Operating voltage 24VDC
Air volume 100m
3
/h
Rated power 9W
Size 3
Operating voltage 24VDC
Air volume 230m
3
/h
Rated power 26W
Size 4
Note:
By reversing the fan motor, the air direction
can be changed from “Inlet Filter Fan mode
to “Exhaust Filter Fan mode** (except for the
types 7F.50.8.xxx.4370, 7F.50.8.xxx.5500 and
7F.50.8.xxx.5630).
** Supplied in “Inlet Filter Fan mode (Standard).
Fan data
Air volume (free flow) m
3
/h 100 230
Air volume (with exhaust filter installed) m
3
/h 75 180
Noise level dB (A) 45 61
Life time at 40°C h 50000 50000
Electrical data
Operating voltage VDC 24 24
Current consumption A 0.37 1.08
Rated power W 9 26
Other data
Housing, cover Plastics according to UL94V-0, light gray (RAL7035)
Filter mat (included) EU3 according to DIN24185, filtering degree (80…90)%
Filter material Synthetic fibre with progressive construction, temperature
resistant to 100°C, self extinguishing, Class F1 (DIN53438)
Electrical connections/wire size 2-pole screw terminals/max. 2.5mm
2
Screw torque Nm 0.8
Ambient temperature range °C –10…+70
Protection class I
Protection category according to EN60529 IP54
Approvals (according to type)