Datasheet

II-2015, www.findernet.com
1
E
7P
SERIES
7P SERIES
Surge Protection Device (SPD)
SPD Type 1+2 Surge arrester range high
discharge capability with no following
current- single/three phase systems
Surge arresters, suitable for low-voltage
applications, to protect equipment against
overvoltage by direct lightning strike, induced
overvoltage and switching overvoltage
To be installed at the boundary of LPZ0- LPZ1
zones or higher
Versions with combination of varistor and high-
performance gas discharge tube (GDT) ensures high
discharge currents and eliminates leakage currents
No follow current
Very low residual voltage
Low U
p
voltage
Replaceable modules
Upside down mounting possible (thanks to dual
terminal markings and new restraint system for
the replaceable module that permits its inversion)
Visual fault signalling: Healty/Replace
Double screw terminal
Remote status signalling contact:
Healty/Replace/Presence. Connector 07P.01 included
According to EN61643-11
35mm rail EN60715 mounting, 36mm each pole
7P.09.1.255.0100 SPD Type 1, GDT protection for
N-PE application only, for 3+1
configuration
7P.01.8.260.1025 SPD Type 1+2, varistor + GDT
unipolar protection suitable to
realize single phase or three phase
systems (230/400V) with the GDT
protection module (7P.09)
7P.02.8.260.1025 SPD Type 1+2 for single phase
system. Varistor + GDT protection
L-N + GDT protection N-PE
7P.09.1.255.0100 7P.01.8.260.1025 7P.02.8.260.1025
SPD Type 1
Spark gap module for N-PE
application in three phase
system, 3+1 configuration
Remote contact signalling of
GDT presence
Upside down mounting possible
Replaceable modules
SPD Type 1+2
Combination of varistor and
encapsulated spark gap (for
single or three phase systems)
Visual fault and remote
contact fault signalling
varistor/GDT status
Upside down mounting possible
Replaceable modules
SPD Type 1+2
Combination of varistor and
encapsulated spark gap (for
single phase systems)
Visual fault and remote contact
fault signalling varistor/GDT
status, N-PE GDT presence
Upside down mounting possible
Replaceable modules
7P.01.8.260.1025
For outline drawing see page 13
SPD specification N-PE L-N N-PE
Nominal voltage (U
N
) VAC 230 230
Maximum operating voltage (U
C
) VAC 255 260 260 255
Lightning impulse current (10/350μs) (I
imp
) kA 100 25 25 50
Nominal discharge current (8/20μs) (I
n
) kA 100 30 30 50
Maximum discharge current (8/20μs) (I
max
) kA 100 60 60 100
Voltage protection level (U
p
) kV 1.5 1.5 1.5 1.5
Temporary overvoltage - 120min (TOV) AC 440 440
Ability to independently switch off
the following current (I
fi
) A 100
No following
current
No following
current 100
Response time (t
a
) ns 100 100 100 100
Short-circuit proof at maximum
overcurrent protection kA
rms
50 50
Maximum overcurrent protection (fuse rating gL/gG) 250A 250A
Maximum overcurrent protection for serial connection 125 A gL/gG 125 A gL/gG
Replacement module code 7P.00.1.000.0100 7P.00.8.260.0025 7P.00.8.260.0025 7P.00.1.000.0050
Other technical data
Ambient temperature range °C –40…+80
Protection degree IP20
Wire size solid cable stranded cable
mm
2
1x2.5…1x50 1x2.5…1x35
AWG 1x13…1x1 1x13…1x2
Wire strip length mm 11
Screw torque Nm 4
Remote status signalling contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT) 1 CO (SPDT)
Rated current AAC/DC 0.5/0.1 0.5/0.1 0.5/0.1
Rated voltage VAC/DC 250/30 250/30 250/30
Wire size (07P.01) solid cable stranded cable solid cable stranded cable solid cable stranded cable
mm
2
1.5 1.5 1.5 1.5 1.5 1.5
AWG 16 16 16 16 16 16
Approvals (according to type)

Summary of content (28 pages)