Datasheet

II-2015, www.findernet.com
2
E
7P SERIES
Surge Protection Device (SPD)
7P
SERIES
SPD Type 1+2 Surge arrester range- three
phase high discharge capability with no
following current- system (230/400V)
Surge arresters, suitable for low-voltage
applications, to protect equipment against
overvoltage by direct lightning strike, induced
overvoltage and switching overvoltage
To be installed at the boundary of LPZ0- LPZ1
zones or higher
Combined high energy varistor block and heavy
duty encapsulated spark gap (GDT) ensures high
discharge current and eliminates leakage current
No follow current
Very low residual voltage
Low U
p
voltage
Replaceable modules
Upside down mounting possible (thanks to dual
terminal markings and new restraint system for
the replaceable module that permits its inversion)
Visual fault signalling: Healty/Replace
Double screw terminal
Remote status signalling contact:
Healty/Replace/Presence. Connector 07P.01 included
According to EN61643-11
35mm rail EN60715 mounting, 36mm each pole
7P.03.8.260.1025 SPD Type 1+2 for three phase
system without Neutral (PEN
conductor). Varistor + GDT
protection L1, L2, L3-PEN
7P.04.8.260.1025 SPD Type 1+2 for three phase
system with Neutral. Varistor +
GDT protection L1, L2, L3-N +
spark gap protection N-PE
7P.05.8.260.1025 SPD Type 1+2 for three phase
system with Neutral. Varistor +
GDT protection L1, L2, L3-N +
varistor + GDT protection N-PE
7P.03.8.260.1025 7P.04.8.260.1025 7P.05.8.260.1025
SPD Type 1+2
3 x combined varistor and
encapsulated spark gap
Visual fault and remote
contact fault signalling
varistor/GDT status
Upside down mounting position
Replaceable modules
SPD Type 1+2
3 x combined varistor and
encapsulated spark gap + 1
encapsulated spark gap
Visual fault and remote contact
fault signalling varistor/GDT
status, N-PE GDT presence
Upside down mounting position
Replaceable modules
SPD Type 1+2
4 x combined varistor and
encapsulated spark gap
Visual fault and remote
contact fault signalling
varistor/GDT status
Upside down mounting position
Replaceable modules
For outline drawing see page 13, 14
SPD specification L-PEN L-N N-PE L, N-PE
Nominal voltage (U
N
) VAC 230 230 230
Maximum operating voltage (U
C
) VAC 260 260 255 260
Lightning impulse current (10/350μs) (I
imp
) kA 25 25 100 25
Nominal discharge current (8/20μs) (I
n
) kA 30 30 100 30
Maximum discharge current (8/20μs) (I
max
) kA 60 60 100 60
Voltage protection level (U
P
) kV 1.5 1.5 1.5 1.5
Temporary overvoltage - 120min (TOV) AC 440 440 440
Ability to independently switch off
the following current (I
fi
) A
No following
current
No following
current 100
No following
current
Response time (t
a
) ns 100 100 100 100
Short-circuit proof at maximum
overcurrent protection kA
rms
50 50 50
Maximum overcurrent protection (fuse rating gL/gG) 250A 250A 250A
Maximum overcurrent protection for serial connection 125A gL/gG 125A gL/gG 125A gL/gG
Replacement module code 7P.00.8.260.0025 7P.00.8.260.0025 7P.00.1.000.0100 7P.00.8.260.0025
Other technical data
Ambient temperature range °C –40…+80
Protection degree IP20
Wire size solid cable stranded cable
mm
2
1x2.5…1x50 1x2.5…1x35
AWG 1x13…1x1 1x13…1x2
Wire strip length mm 11
Screw torque Nm 4
Remote status signalling contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT) 1 CO (SPDT)
Rated current AAC/DC 0.5/0.1 0.5/0.1 0.5/0.1
Rated voltage VAC/DC 250/30 250/30 250/30
Wire size (07P.01) solid cable stranded cable solid cable stranded cable solid cable stranded cable
mm
2
1.5 1.5 1.5 1.5 1.5 1.5
AWG 16 16 16 16 16 16
Approvals (according to type)