Datasheet
II-2015, www.findernet.com
3
E
7P
SERIES
7P SERIES
Surge Protection Device (SPD)
SPD Type 1+2 Surge arrester range with high
performance “Low U
p
”- Single phase/three
phase system
• Surge arrester suitable for 230/400V system
applications to prevent overvoltage effects
caused by direct or indirect lightning strikes
• To be installed at the boundary of LPZ0 and
LPZ1 zones
• Low U
p
to protect senstive equipment
• Visual indication of varistor status -
Healthy/Replace
• Contact for remote signalling of varistor status.
Connector 07P.01 included
• Replaceable varistor and Spark Gap modules
• Complies with EN61643-11
• 17.5mm rail EN60715 mounting for each
module
7P.12.8.275.1012 SPD Type 1+2 for single phase
system with Neutral.
• Varistor protection L-N + spark gap protection
N-PE for single phase systems
• Replaceble Spark Gap and varistor modules
7P.13.8.275.1012 SPD Type 1+2 for three phase
system without Neutral (PEN
conductor).
• Varistor protection L1, L2, L3-PEN for three
phase systems
• Replaceable varistor modules
7P.12 / 7P.13
Screw terminals
7P.12.8.275.1012 7P.12.8.275.1012
• SPD Type 1+2
• Replaceble Spark Gap and varistor modules
(for single phase systems)
• Visual and remote signalling of varistor status
• SPD Type 1+2
• Replaceable varistor modules
(for three phase systems)
• Visual and remote signalling of varistor status
For outline drawing see page 14
SPD specification L-N N-PE L-PEN
Nominal voltage (U
N
) VAC 230 — 230
Maximum continous operating voltage (U
C
) VAC/DC 275/350 255/— 275/350
Lightning impulse current (10/350μs) (I
imp
) kA 12.5 25 12.5
Nominal discharge current (8/20μs) (I
n
) kA 30 40 30
Maximum discharge current (8/20μs) (I
max
) kA 60 60 60
Voltage protection level (U
p
) kV 1.2 1.5 1.2
Ability to independently switch off
the following current (I
fi
) A
No following
current 100
No following
current
Response time (t
a
) ns 25 100 25
Short-circuit proof at maximum
overcurrent protection kA
rms
50 — 50
Maximum overcurrent protection (fuse rating gL/gG) 160A — 160A
Replacement module code 7P.10.8.275.0012 7P.10.1.000.0025 7P.10.8.275.0012
Other technical data
Ambient temperature range °C –40…+80
Protection degree IP20
Wire size solid cable stranded cable
mm
2
1x1…1x35 1x1…1x25
AWG 1x17…1x2 1x17…1x4
Wire strip length mm 12
Screw torque Nm 3
Remote status signalling contact specification
Contact configuration 1 CO (SPDT) — 1 CO (SPDT)
Rated current AAC/DC 0.5/0.1 — 0.5/0.1
Rated voltage VAC/DC 250/30 — 250/30
Wire size (07P.01) solid cable stranded cable solid cable stranded cable
mm
2
1.5 1.5 — 1.5 1.5
AWG 16 16 — 16 16
Approvals (according to type)