Datasheet

II-2015, www.findernet.com
8
E
7P SERIES
Surge Protection Device (SPD)
7P
SERIES
SPD Type 1+2 and Type 2 Surge arrester range
for Photovoltaic applications
Surge arrester for protection of DC side (1020V)
of systems in photovoltaic applications
Protects equipment against overvoltage
caused by direct lightning strike (Type 1+2
only) and induced overvoltages (Type 1+2 and
Type 2)
7P.26.9.000.x015, U
CPV
=1020VDC (Type 2)
7P.23.9.000.x015, U
CPV
=1020VDC (Type 2)
7P.03.9.000.1012, U
CPV
=1000VDC (Type 1+2)
Visual indication of varistor status -
Healthy/Replace
Contact for remote signalling of varistor status.
Connector (07P.01) included (depending on the
verision)
Replaceable modules
Complies with prEN50539-11:2010
35mm rail (EN60715) mounting
7P.23.9 / 7P.26 / 7P.03
Screw terminals
7P.26.9.000.x015 7P.23.9.000.x015 7P.03.9.000.1012
SPD Type 2 (2 varistors + 1
spark-gap) for 1020VDC
photovoltaic systems
Combination of replaceable
varistor and encapsulated
spark gap modules
Visual and optional remote
connector for signalling of the
varistor status
SPD Type 2 (3 varistors) for
1020VDC photovoltaic
systems
Replaceable varistor modules
Visual and optional remote
connector for signalling of the
varistor status
SPD Type 1+2 (3 varistors)
for 1000VDC photovoltaic
systems
Replaceable varistor modules
Visual and remote signalling
of varistor status
For outline drawing see page 15
SPD specification
Varistor
module
Spark-gap
module
Varistor
module
Varistor
module
Maximum operating voltage (U
CPV
) VDC 1020 1020 1000
Maximum operating voltage/per module (U
CPV
) VDC 510 1020 510 500
Lightning impulse current (10/350μs)/
per module (I
mp
) kA 12.5
Nominal discharge current/
per module (8/20μs) (I
n
) kA 15 15 15 30
Maximum discharge current/
per module (8/20μs) (I
max
) kA 30 30 30 60
Voltage protection level/per module (U
p
) kV 2 2.5 2 1.8
Voltage protection level of the system
U
p
(+–)/(+/–PE) kV 4/2.5 4/4 3.6/3.6
Response time (t
a
) ns 25 100 25 25
Short circuit current withstand I
SCPV
A 125 125 125
Replacement module code 7P.20.9.500.0015 7P.20.1.000.9015 7P.20.9.500.0015 7P.00.9.500.0012
Other technical data
Ambient temperature range °C –40…+80
Protection degree IP20
Wire size solid cable stranded cable solid cable stranded cable
mm
2
1x1…1x35 1x1…1x25 1x2.5…1x50 1x2.5…1x35
AWG 1x17…1x2 1x17…1x4 1x13…1x1 1x13…1x2
Wire strip length mm 14 9
Screw torque Nm 3 4
Remote status signalling contact specification
Contact configuration 1 CO (SPDT) 1 CO (SPDT) 1 CO (SPDT)
Rated current AAC/DC 0.5/0.1 0.5/0.1 0.5/0.1
Rated voltage VAC/DC 250/30 250/30 250/30
Wire size (07P.01) solid cable stranded cable solid cable stranded cable solid cable stranded cable
mm
2
1.5 1.5 1.5 1.5 1.5 1.5
AWG 16 16 16 16 16 16
Approvals (according to type)