Datasheet

H
Mono-function timer range
80.61 - Power off-delay (True off-delay),
multi-voltage
80.82 - Star-delta, multi-voltage
17.5 mm wide
Rotary range selector, and timing trimmer
Four time scales from 0.05s to 3 min (type 80.61)
Six time scales from 0.1s to 20min (type 80.82)
High input/output isolation
35mm rail (EN60715) mount
80.61 / 80.82
Screw terminal
80.61 80.82
Multi-voltage
Mono-function
Multi-voltage
Mono-function
Transfer time can be regulated (0.05…1)s
BI: Power off-delay (True off-delay) SD: Star-delta
Wiring diagram
(without control signal)
Wiring diagram
(without control signal)
For UL ratings see:
General technical informationpage V
For outline drawing see page 6
Contact specification
Contact configuration 1 CO (SPDT) 2 NO (DPST-NO)
Rated current/Maximum peak current A 8/15 6/10
Rated voltage/
Maximum switching voltage V
AC 250/400 250/400
Rated load AC1 VA 2000 1500
Rated load AC15 (230VAC) VA 400 300
Single phase motor rating (230VAC) kW 0.3
Breaking capacity DC1: 30/110/220 V A 8/0.3/0.12 6/0.2/0.12
Minimum switching load mW (V/mA) 300 (5/5) 500 (12/10)
Standard contact material AgNi AgNi
Supply specification
Nominal voltage (U
N
) VAC (50/60Hz) 24…240 24…240
VDC 24…220 24…240
Rated power AC/DC VA (50Hz)/W <0.6/<0.6 <1.3/<0.8
Operating range VAC 16.8…265 16.8…265
VDC 16.8…242 16.8…265
Technical data
Specified time range (0.05…2)s, (1…16)s, (8…70)s, (50…180)s (0.1…2)s, (1…20)s, (0.1…2)min, (1…20)min
Repeatability % ±1 ±1
Recovery time ms 100
Minimum control impulse ms 500 (A1-A2)
Setting accuracy-full range % ±5 ±5
Electrical life at rated load in AC1 cycles 100·10
3
60·10
3
Ambient temperature range °C –10…+50 –10…+50
Protection category IP 20 IP 20
Approvals (according to type)
4
II-2016, www.findernet.com
80 SERIES
Modular timers 6- 8A
80