Single Zone Service Manual - General

Part 4 Trouble Shooting
- 38 -
Measure resistance
Refer to Check Point
Resistance is adequate?
Sensor OK
Resistance (White)
200~165@25~30°C
Resistance (Black)
10~8@25~30°C
Resistance (Blue)
5~4@25~30°C
Yes
No
Replace Sensor
Discharge Pipe Temp Sensor (200)
Air/Room Temp. Sensor (10)
Indoor Pipe Temp. Sensor (5)
Check Point
1. 10k Ω / at 25℃(77℉)±10%
2. 5k Ω / at 25℃(77℉)±10%
3. 200k Ω / at 25℃(77℉)±10%
Check Method
For more information, please refer to the 38 page table.