Single Zone Service Manual - General

Part 4 Trouble Shooting
- 39 -
Resistance - Temp. Sensor Table
Temp (℃/℉)
Resistance(KΩ)
Air Sensor s-Pipe Sensor D-Pipe Sensor
-30/-22 204.35 102.17 -
-25/-13 146.97 73.49 -
-20/-4 107.09 53.55 -
-15/5 79 3950 -
-10/14 58.95 29.48 -
-5/23 44.47 22.24 -
0/32 33.9 16.95 585.66
5/41 26.09 13.05 465.17
10/50 20.27 10.14 372.49
15/59 15.89 7.94 300.58
20/68 12.55 6.28 244.33
25/77 10 5 200
30/86 8.03 4.01 164.79
35/95 6.49 3.24 136.64
40/104 5.28 2.64 113.98
45/113 4.32 2.16 95.62
50/122 3.56 1.78 80.65
55/131 2.95 1.48 68.38
60/140 2.46 1.23 58.27
65/149 2.06 1.03 49.88
70/158 1.74 0.87 42.9
75/167 1.47 0.74 37.05
80/176 1.25 0.63 32.14
90/194 0.92 0.46 24.46
100/212 0.68 0.34 18.89