Accessory RT6 Manual (2019)

Configuration Mode Settings
5. Staged Off Outputs (For HP 0 and HP B only)
Select whether the outputs for heating and cooling are staged off
independently or are satisfied simultaneously.
1 = outputs staged off independently
0 = outputs off simultaneously
Press the up or down button to set.
Press the right button to advance to the next screen.
4. 2
nd
Stage Temperature Differential (1°F to 5°F) (0.5°C to 2.5°C) (For HP 0
and HP B only)
Set the number of degrees between when stage 1 turns on and when stage
2 turns on.
Press the up or down button to set differential value.
Press the right button to advance to the next screen.
3. 1
st
Stage Temperature Differential (1°F to 5°F) (0.5°C to 2.5°C)
Set the number of degrees between your “setpoint” temperature and your
“turn on” temperature.
Press the up or down button to set differential value.
Press the right button to advance to the next screen.
2. Temperature Scale (F or C)
Choose Fahrenheit or Celsius.
Press the up or down button to select.
Press the
right
button to advance to the next screen.
1. System – Set for heat pump, non-heat pump, reversing valve operation
Operating Modes
There are three possible operating modes for the RT6. Off, Heat, and Cool modes are accessed by pressing the
SYS (left) button.
OFF Mode
In this mode, the thermostat will not turn on the heating or cooling
devices
Note: The indoor fan can be turned on manually in every operating
mode by pressing the FAN (right) button. The word FAN
shows on the display and the fan icon appears when the fan
operates.
OFF
Heat Mode
In this mode, the thermostat controls the heating system. When the heat
outputs, the flame icon apprears on the display.
Note: For heat pumps, there is a four minute delay for your
compressor to restart after it has turned off. To bypass the
compressor time delay, go to OFF mode for 5 seconds.
Cool Mode
In this mode, the thermostat controls the cooling system. When the
cooling outputs, the snowflake icon apprears on the display.
Note: There is a four minute delay for your compressor to restart after
it has turned off. To bypass the compressor time delay, go to
OFF mode for 5 seconds.
LIAF249
Friedrich Air Conditioning Co.
Post Office Box 1540 San Antonio, Texas 78295-1540
4200 N. Pan Am Expressway San Antonio, Texas 78218-5212
(210) 357-4400 FAX (210) 357-4480
www.friedrich.com
Mode of Operation
The RT6 is a 1-stage or 2-stage heat thermostat. It functions with air conditioning, heat pumps, or
electric heat systems.
The thermostat activates the heating appliance when the room temperature is below the set heat
temperature (by the differential temperature). The RT6 will stop outputting when the call for heat has
been satisfied. With heat pumps, the thermostat will not let the compressor come on for 4 minutes
after it turns off. This protects your compressor.
When the room temperature is greater than the set cool temperature (by the differential temperature),
the cooling device is activated. The RT6 will stop outputting when the call for cooling is satisfied.
The thermostat will not let the compressor come on for 4 minutes after it turns off. This protects your
compressor.
The RT6 has three possible operating modes: OFF, Heat, and Cool mode. In off mode, the
thermostat will not turn on heating or cooling devices. The manual fan can be turned on in all
operating modes using the fan button. In heat mode, the thermostat controls the heating system. In
the cool mode, the thermostat controls the cooling system.
6. Auxiliary Delay ON – (0-30 minutes) (For HP 0 and HP B only)
Set the delay time in minutes for auxiliary heat to be locked out after a call
for second stage. This extra savings feature is used to temporarily lock out
auxiliary heat devices, allowing just heat pump to try to satisfy heat call.
Press the up or down button to select.
Press the right button to advance to the next screen.
7. (45°F to 90°F) (7°C to 32°C)
Adjust to control the maximum heat set temperature allowed.
Press the or button to select.
Press the button to advance to the next screen.
8. Minimum Cool Setpoint (45°F to 90°F) (7°C to 32°C)
Adjust to control the minimum cool set temperature allowed.
Press the up or down button to select.
Press the right button to advance to the next screen.
9. (+9°F to -9°F) (+4.5°C to -4.5°C)
Adjust to calibrate displayed room temperature to match actual room
temperature.
When not set to 0, will display.
Press the or button to select.
Press the button to advance to the next screen.
Button Functions
UP – Used to increase the set temperatures and to adjust configuration settings.
DOWN – Used to decrease the set temperatures and to adjust configuration settings.
SYS (left) – Used to change from OFF, HEAT, and COOL modes
FAN (right) – Used to turn on and off the indoor fan.
SYStem (left)
(right)
Down button
Up button
Heat Set Point
Use the SYS button to select Heat Mode. Press the up or down button to view the
current heat set point larger on the display. When the large set point is displayed,
the HEAT icon will blink. The up or down buttons can be used to adjust the set point.
After 5 seconds of inactivity the screen will display the room temperature and the
HEAT icon will not blink.
HEAT icon will blink.
Cool Set Point
Use the SYS button to select Cool Mode. Press the up or down button to
view the current cool set point larger on the display. When the large set
point is displayed, the COOL icon will blink. The up or down buttons can
be used to adjust the set point. After 5 seconds of
inactivity the screen will display the room
temperature and the COOL icon will not blink.
COOL icon will blink.
Set Point Adjustment
Troubleshooting
Symptom Remedy
No display Check for 24 VAC at thermostat; display is blank when 24 VAC
is not present
All thermostat buttons are
inoperative
Verify 24 VAC is present; unit locks out when 24 VAC is not
present
No response with first button press First button press activates backlight only
Thermostat turns on and off too
frequently
Adjust temperature differential
(see Configuration Mode Settings 3 & 4)
Fan runs continuously Press FAN (right) button to turn fan off
Room temperature is not correct Calibrate thermostat (see Configuration Mode Setting 10)
Heat or Cool not coming on Verify wiring is correct, gently pull on each wire to verify there
is a good connection at terminal block
HEAT blinking In heat set point screen, this is normal operation
COOL blinking In cool set point screen, this is normal operation
Problem not listed above Press Reset button once*
* Reset Button Function:
Display is refreshed, configuration settings are unchanged.
Testing the Thermostat
Once the thermostat is configured, it should be thoroughly tested.
CAUTION!
:
Do not energize the air conditioning system when the outdoor temperature is below
50 degrees. It can result in equipment damage or personal injury.
Fan Test
1. Press FAN (right) button. Fan displays. Indoor fan turns ON.
2. Press FAN (right) button. Indoor fan turns OFF.
OFF
Cool Test
1. Press SYS (left) button until cool mode is displayed.
2. Adjust set temperature so it is 5 degrees below room temperature.
3. A/C should come on within a few seconds.
4. Adjust the set temperature 2 degrees above the room temperature and
the A/C should turn off. There may be a fan delay on your system.
Note:
There is a four-minute time delay to protect the compressor after it .
To bypass the compressor time delay, go to OFF mode for 5 seconds.
Heat Test
1. Press SYS (left) button until heat mode is displayed.
2. Adjust the set temperature so it is 5 degrees above the room temperature.
3. Heat should come on within a few seconds.
4. Adjust the set temperature 2 degrees below the room temperature and the
heat should turn off. There may be a fan delay on your system.
Note:
For heat pumps, there is a four-minute delay to protect your compressor after it turns off.
To bypass the compressor time delay, go to OFF mode for 5 seconds.
Press the up or down button to select.
Press the right button to advance to the next screen.
System Setting Reversing Valve Setting
Heat Pump
HP ‘O’ O - Energized in Cooling
Heat Pump
HP ‘B’ B - Energized in Heating
Heat/Cool and Single-
Stage Heat Pump Only
ELC N/A
To setup screens for configuration mode are as follows: