Product Manual

29
EN
Relay Activate relay, relay settings, relay test
* these are only shown if the 'E-Manager' function has been activated under 'Relay mode'.
Relay mode
for selecting the different functions of the floating switch contact in the data communication
area:
- Alarm function
- Active output
- Energy-Manager
Relay test
Function test to determine whether the floating switch contact switches
Switch-on point (only if 'Energy-Manager' function is activated)
for setting the effective power limit beyond which the floating switch contact is switched on
Switch-off point (only if 'Energy-Manager' function is activated)
for setting the effective power limit beyond which the floating switch contact is switched off
Energy-Manager
(in Relay menu
item)
The 'Energy-Manager' function can be used to activate the floating switch contact in such
a way that it functions as an actuator.
Thus a consumer that is connected to the floating switch contact can be controlled by spec-
ifying a switch-on or switch-off point that depends on the feed-in power.
Setting range Relay mode / Relay test / Switch-on point* / Switch-off point*
Setting range ALL / Permanent / OFF / ON / E-Manager
Factory setting ALL
Alarm function:
Permanent /
ALL:
Switch the floating switch contact for permanent and temporary ser-
vice codes (e.g. brief interruption to energy being fed into the grid, a
service code occurs a certain number of times a day - can be adjusted
in 'BASIC' menu)
Active output:
ON: The floating NO contact is on all the time the inverter is in operation
(as long as the display is not dark and is displaying something).
OFF: The floating NO contact is off.
Energy-Manager:
E-Manager: Further details on the 'Energy-Manager' function may be found in the
"Energy-Manager" section.
Factory setting 1000 W
Setting range Switch-off point - max. nominal output of inverter / W / kW
Factory setting 500
Setting range 0 - Switch-on point / W / kW