Product Manual

42
- Insulation fault:
for activating and deactivating insulation monitoring, with error message and imme-
diate shutdown of the inverter if there is an insulation fault
ON / OFF (depends on the country setup)
- Threshold error:
for setting an insulation threshold at which the inverter produces an error message
and interrupts the feeding of energy into the grid
0 - 1000 kOhm (depends on the country setup)
Temperature warning
for activating / deactivating the overtemperature warning for each event;
the overtemperature warning is sent and displayed on the monitor.
ON / OFF
TOTAL Reset
in the LOG menu item, resets the max. and min. voltage values and the max. power of
feeding in to zero.
Once values have been reset, this action cannot be undone.
To reset the values to zero, press the 'Enter' key.
"CONFIRM" is displayed.
Press 'Enter' again.
The values are reset and the menu is displayed