Installation Manual

55
Field Adjustable Trip Points
Setup 208 V Setup 220 V
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U < 50% 104 0.16
9
110 0.16
9
50 U < 88 % 183 2
118
194 2
118
110 < U < 120 % 229 1
58
242 1
58
U 120 % 249 0.16
9
264 0.16
9
U
Imin
adjustable 104 - 198 0.016 - 21.0
1 - 1260
104 - 209 0.016 - 21.0
1 - 1260
U
Imax
adjustable 218 - 288 0.016 - 21.0
1 - 1260
231 - 288 0.016 - 21.0
1 - 1260
U
Omax
adjustable 218 - 288 0.016 - 4.25
1 - 255
231 - 288 0.016 - 4.25
1 - 255
U
Omin
adjustable 104 - 198 0.016 - 4.25
1 - 255
104 - 209 0.016 - 4.25
1 - 255
Setup 240 V, Setup HI1 Setup 50HZ
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U
AC
[V] Clearing Time [s]
Clearing Time [cyl]
U < 50% 120 0.16 / 0.5 ***
9 / 28 ***
110 0.16
8
50 U < 88 % 211 2 / 21 ***
118 / 1258 ***
194 2
100
110 < U < 120 % 264 1
58
242 1
50
U 120 % 288 0.16
9
264 0.16
8
U
Imin
adjustable 104 - 228 0.016 - 21.0
1 - 1260
104 - 209 0.016 - 21.0
1 - 1050
U
Imax
adjustable 252 - 288 0.016 - 21.0
1 - 1260
231 - 288 0.016 - 21.0
1 - 1050
U
Omax
adjustable 252 - 288 0.016 - 4.25
1 - 255
231 - 288 0.016 - 4.25
1 - 212
U
Omin
adjustable 104 - 228 0.016 - 4.25
1 - 255
104 - 209 0.016 - 4.25
1 - 212
*** Setup HI1