Status Diagnosis and Troubleshooting
Displaying Sta-
tus Codes
Your inverter is equipped with a self diagnostic system that automatically identifies a large
number of possible operation issues by itself and displays them on the screen. This en-
ables you to know immediately if there are any malfunctions in the inverter, the photovoltaic
system or any installation or operating errors.
Whenever the self diagnostic system has identified a particular issue, the respective status
code is shown on the screen.
Total Failure of
the Display
If the display remains dark for a long time after sunrise:
- check the AC voltage at the inverter's connections:
the AC voltage must be 208–240 V (+10% / -12%) according to the grid.
Class 1 Status
Codes
Status codes in class 1 are typically temporary. Their cause lies in the grid.
Example: the grid frequency is too high and the inverter is not permitted to feed energy into
the grid because this would not comply with a standard. No device fault has occurred.
The inverter will first respond by disconnecting from the grid. Then, the grid will be checked
for the duration of the observation period stipulated. If, after the end of this period, no fur-
ther defect is identified, your inverter resumes operating and feeding energy into the grid.
The GPIS soft start function is activated depending on the country setup:
according to national guidelines, the output of the inverter increases continuously after a
shutdown due to an AC error.
Class 2 Status
Codes
IMPORTANT! Status codes may sometimes appear briefly as a result of the control re-
sponse from the inverter. If it subsequently continues to operate normally, there has not
been a system error.
Code Description Behavior Remedy
102 AC voltage too high
Grid conditions are being test-
ed and as soon as they are
again within the permissible
range, the inverter will resume
feeding power into the grid.
Check grid connections.
If this status code keeps recur-
ring, contact your system in-
staller.
103 AC voltage too low
105 AC frequency too high
106 AC frequency too low
107 No AC grid detected
108 Stand alone operation detect-
ed
112 RCMU error
Code Description Details Rectification
212 Overvoltage at L1-N Grid conditions are being test-
ed and as soon as they are
back within the permissible
range, the inverter will resume
grid power feed operation.
Check grid connections. If this
status code keeps recurring,
contact your system installer.
213 Undervoltage at L1-N
222 Overvoltage at L2-N
223 Undervoltage at L2-N