Product Manual

55
EN-US
Relevant stan-
dards and direc-
tives
* Only for AFCI and insulation monitoring functions
Output frequency range
Setups: 50 Hz, 60 Hz
Setup: HI1
48.0 - 50.5 Hz / 59.3 - 60.5 Hz
- / 57.0 - 63.0 Hz
Grid frequency setting range 45.0 - 55.0 Hz / 50.0 - 65.0 Hz
Frequency trip limit accuracy 0.05 Hz
Frequency clearing time setting range 0.016 - 600 s
Harmonic distortion < 2.5 %
Power factor (cos phi) 0 - 1 ind./cap..
1)
General Data
Maximum efficiency 97.9 %
CEC efficiency at 208 V
at 220 V
at 240 V
97.0 %
97.0 %
97.0 %
97.0 %
97.0 %
97.0 %
97.0 %
97.0 %
97.0 %
Self-consumption at night at 208 V
at 220 V
at 240 V
0.4 W
0.6 W
0.6 W
Self-consumption during operation 10 W
Cooling Forced-air ventilation
Protection class NEMA4X
Dimensions h x w x d 28.5 x 20.1 x 8.9 inch
(725 x 510 x 225 mm)
Weight 82.5 lbs. (37.4 kg)
Shipping dimensions w x h x d 31.1 x 22.6 x 13.4 inch
(790 x 575 x 340 mm)
Shipping weight 90.2 lbs. (40.9 kg)
Permissible ambient temperature
(at 95% rel. humidity)
-40 °F - +140 °F (-40 °C - +60°C)
Permissible storage temperature
(with 95% rel. humidity)
-40 °F - +158 °F (-40 °C - +70°C)
Protection Devices
Insulation monitoring Integrated
Stand-alone operation protection Integrated
Reverse polarity protection Integrated
Arc detection/interruption Integrated
Overtemperature Operating point shift / active cooling
1) ind. = induktiv cap. = kapazitiv
Fronius Primo 11.4-1 208-240 12.5-1 208-240 15.0-1 208-240
- UL 1741
- IEEE 1547
- IEEE 1547.1
- UL 1998 *
- CSA TIL M07 Issue 1
- ANSI/IEEE C62.41
- UL 1699B Issue 2
- FCC Part 15 A & B
- NEC Article 690
- C22.2 no 107.1-01