iCommand-Touch Manual

CAP-837
2.7.6
"Factory settings" menu
Fig. 47: "Factory settings" screen
Parameter
Value setting/Initial setting/Remarks
Start-up time
Specifies the start
Setting range: 3
Initial setting: depending on compressor type
Off time
Specifies the minimum run
switch off of the compressor. This value is also used
during restart delays after power failure.
Setting range: 0
Initial setting: 120 s
Run on time
Specifies the run on time of the compressor in
automatic opera
switching operations.
Setting range: 10
Initial setting: depending on compressor type
Final temperature
min.
Specifies the minimum start temperature of the
compressor
Setting range: 32
Initial setting: 41 °F
Final temp.
warning
Specifies the upper threshold for the compressors final
temperature.
Setting range: 194
Initial setting: 221 °F
Final temperature
limited to
Specifies the switch
compressors final temperature (fault).
Setting range: 212
Initial setting: 230 °F
iCommand
43
"Factory settings" menu
In the "Factory settings" menu the operating times and final compre
sor temperature are displayed.
Value setting/Initial setting/Remarks
Compressor
type
Specifies the start
-up time of the motor.
Setting range: 3
– 30 s
Initial setting: depending on compressor type
All
Specifies the minimum run
on time during manual
switch off of the compressor. This value is also used
during restart delays after power failure.
Setting range: 0
– 120 s
Initial setting: 120 s
All
Specifies the run on time of the compressor in
automatic opera
tion or when exceeding the specified
switching operations.
Setting range: 10
– 3600 s
Initial setting: depending on compressor type
All
Specifies the minimum start temperature of the
Setting range: 32
– 50 °F
Initial setting: 41 °F
All
Specifies the upper threshold for the compressors final
temperature.
Setting range: 194
– 230 °F
Initial setting: 221 °F
All
Specifies the switch
-off threshold for the
compressors final temperature (fault).
Setting range: 212
– 248 °F
Initial setting: 230 °F
All
iCommand – Touch
iCommand
- Touch
In the "Factory settings" menu the operating times and final compre
s-
Compressor
State
Display
Display
Display
Display
Display
Display