iCommand-Touch Manual

CAP-837
Fig. 51: "LLC configuration" screen
(Part 1/2)
Fig. 52: "LLC configuration" screen
(Part 2/2)
Parameter
Value setting/Initial setting/Remarks
Lead lag control
Indicates if and how the communication for
function should be done (or if a LLC module is avai
able).
Setting range:
No (no LLC)
Digital (LLC via expansion module)
RS485 (LLC via RS485 connection)
When selecting "Digital" a LLC module is
expected at address 2
Initial setting: No
Baud rate Baud rate
for communication on LLC via RS485
Setting range: 4800 / 9600 / 19200 / 38400 / 57600 /
115200
Initial setting: 19200
Change immedi-
ately
Specifies if the LLC series rotates immediately after
the change interval is completed (recommended) or
only when the switch
reached. Warning: If No, the change interval can be
iCommand
45
Individual settings (e.g. switch-on times, switch-
off and change inte
vals) can be set in the "LLC configuration" (Fig.
50
Using the
button the second part of the menu can be screen
(Fig. 52) accessed.
Value setting/Initial setting/Remarks
Compressor
type
Indicates if and how the communication for
the LLC
function should be done (or if a LLC module is avai
l-
Setting range:
No (no LLC)
Digital (LLC via expansion module)
RS485 (LLC via RS485 connection)
When selecting "Digital" a LLC module is
expected at address 2
Initial setting: No
All
for communication on LLC via RS485
Setting range: 4800 / 9600 / 19200 / 38400 / 57600 /
Initial setting: 19200
All
Specifies if the LLC series rotates immediately after
the change interval is completed (recommended) or
only when the switch
-on or switch-off threshold is
reached. Warning: If No, the change interval can be
All
iCommand – Touch
iCommand
- Touch
off and change inte
r-
50
) screen.
button the second part of the menu can be screen
Compressor
State
Display
Display
Display