iCommand Manual

CAP-836
iCommand
24
Value Designation Description
0 On-site operation
The compressed air generation
can only be switched on or off on
the control con
sole/display of the
ICOMMAND -
BASIC.
1 Remote control
The compressed air generation
can only be switched on via a
positive edge (24 VDC) on
terminal 23 and switched off via
low level (0 V) on terminal 23 or
via the
key. This functionality
is identified by the flashing text
on the display of
ICOMMAND -
BASIC. If the
key is pressed on the system on
site, the system switches off after
120 seconds and for safety
reasons, it can only be started via
remote control
after the
has been pressed
(acknowledgement) on
also applies for a start via PLANT
CONTROL V/T.
2 BLS-OK
The input on terminal 23 serves to
report the operational readiness of
an external controller. Only with
an existing high level (24
can the external controller switch
between load operation and idle.
During existing low level, the BLS
operation is switched off
automatically and the internal
pressure sensor is used.
iCommand
- Basic
The compressed air generation
can only be switched on or off on
sole/display of the
BASIC.
The compressed air generation
can only be switched on via a
positive edge (24 VDC) on
terminal 23 and switched off via
low level (0 V) on terminal 23 or
key. This functionality
is identified by the flashing text
on the display of
BASIC. If the
key is pressed on the system on
-
site, the system switches off after
120 seconds and for safety
reasons, it can only be started via
after the
key
has been pressed
(acknowledgement) on
-site. This
also applies for a start via PLANT
CONTROL V/T.
The input on terminal 23 serves to
report the operational readiness of
an external controller. Only with
an existing high level (24
VDC)
can the external controller switch
between load operation and idle.
During existing low level, the BLS
operation is switched off
automatically and the internal
pressure sensor is used.