CAP-837 June, 2015 Rev. B Nx Series iCommand – Touch Controller OPERATOR MANUAL WARNING Personal injury and/or equipment damage will be result by failing to pay attention to the vital safety information and instructions in this manual. Carefully read, understand, and retain all safety information and instructions before operating this compressor.
General information Limitation of liability Information on these operating instructions All information and instructions in this manual have been compiled taking account of the applicable standards and regulations, state-of-the-art technology and our years of knowledge and experience. These instructions enable you to use the machine safely and efficiently. The instructions are a component part of the machine and must be accessible for staff at all times.
Table of contents 1 Safety .......................................................................................................................................................5 1.1 Symbols in these instructions .........................................................................................................5 1.2 Proper use ......................................................................................................................................6 1.3 General safety ..............
Safety 1 Safety This section is a summary of import ant safety aspects to ensure optimum protection of the personnel and safe and trouble-free operation. CAUTION! This combination of symbol and signal word indicates a possibly hazardous situation which may cause minor or light injuries if not avoided. The owner, lessor or operator of this compressor is hereby notified a nd forewarned that failure to observe these safety precautions may result in injury and/or property damage.
Safety 1.2 Proper use Warning – high-voltage. The machine is designed and constructed exclusively for the proper use described here. Warning – explosive substances. The screw compressor serves exclusively to generate compressed air in an environment not subject to explosion. The screw compressor must be supplied exclusively with cool, dry and dust-free cooling air. Warning – danger zone. Do not operate the compressor in excess of its rated pressures and speeds indicated on the compressor nameplate.
Safety 1.3 General safety 1.4 Safety devices 1. Read and understand all the instructions found in this manual before operating your compressor. 2. Disconnect the main power source before working on or performing any maintenance procedures on this unit. Use a lock out and tag out process. 3. Do not attempt to remove any parts, break any connection, loosen oil fill plug or drain plug until the unit has been shut down and air pressure has been relieved. 4.
Safety Do not change the pressure setting of the pressure relief valve, restrict the function of the relief valve or replace the relief valve with a plug. 1.4.2 Description of the installed safety devices Emergency stop button 1.5 Environmental protection NOTICE! Danger to the environment from incorrect handling of pollutants! Incorrect handling of pollutants, particularly incorrect waste disposal, may cause serious damage to the environment. Fig.
Safety Hazardous Voltage 1.6 Instructions on the machine WARNING! Danger of symbols! injury from illegible Stickers and signs can become dirty or otherwise obscured over time, with the result that dangers cannot be recognized and the necessary operating instructions cannot be complied with. This, in turn, poses a risk of injury. - All safety, warning and operating instructions must always be maintained in a completely legible condition. - Damaged signs or stickers must be replaced immediately.
Safety Brief instructions for operation This sticker is on the enclosure and contains brief instructions for operation.
iCommand – Touch iCommand - Touch 2 ICOMMAND - TOUCH 2.1 Overview of the ICOMMAND - TOUCH No. Key/icon Description of function 1 Display Displays settings and operating parameters. 2 Serves to switch on the compressor. 3 Serves to switch off the compressor. During the start, the control displays for about three seconds, a welcome screen. The display changes automatically to the basic display. The control unit has a resistant color touch screen.
iCommand – Touch iCommand - Touch 2.3 Overview Safety pressure CAP-837 Operating modes Three operating modes can be set using the controller. Operating mode Description Automatic operation After reaching the switch-off pressure, the system switches to idle for the duration of the idle time (run-on). After the run-on time has elapsed, the motor switches off. The compressor can start up by itself at any time if the machine drops below the switch-on pressure.
iCommand – Touch iCommand - Touch 2.4 Display structure Overview Fig. 3: ICOMMAND - TOUCH basic display This illustration contains, for illustration purposes, a combination of symbols, which are not possible in a real system. The settings and operating parameters are shown in the display. Five buttons (Fig. 3/5–9) are located on the right-hand side of the basic display, which allows access to all important functions and information for the system.
iCommand – Touch iCommand - Touch No. Key/ic on 1 2 Description of function This symbol shows the current system state. "State" Display of the current screen 3 By tapping the "Information" button a switch occurs into the type plate. 4 This button is used to select the display language in the basic display. 5 Button with display of the current pressure and to open the "Pressure" screen. 6 Button with display of the current temperature and to open the "Temperature" screen.
iCommand – Touch iCommand - Touch 17 Motor runs display 18 "Remote" display: Remote On/Off is activated "Restart" display: Automatic restart is activated CAP-837 19 Button "?" to open the symbol explanation 20 State display 21 If this symbol is shown, then the compressor is an inverter.
iCommand – Touch iCommand - Touch System state The current state of the system is shown in all display pages in the upper left corner via the following three symbols: No message is present, if the smiley face is shown. The system functions flawlessly. As soon as a warning or maintenance message is present, the smiley face is replaced by a flashing warning triangle. The flashing tool signals a fault (the compressor is switched off).
iCommand – Touch iCommand - Touch Buttons in the basic display The buttons in the basic display are allocated as follows: "Pressure" (Fig. 4/1) button to open the "Pressure" screen "Temperature" (Fig. 4/2) button to open the "Temperature" screen "State" (Fig. 4/3) button to open the "State" screen "Graphics" (Fig. 4/4) button to open the "Graphics" screen "Menu" (Fig. 4/5) button to open the "Menu" screen Fig.
iCommand – Touch iCommand - Touch "Air circuit" and "Oil circuit" screen Tap the "State" button and the compressor stage is shown. The air circuit and oil circuit are displayed schematically. Fig. 8: "Air circuit" screen Tap the button to the "right" to get to the "Oil circuit" screen. Fig. 9: "Oil circuit" screen "Graphics" screen The "Graphics" button initially leads to an overview of all existing graphical evaluation.
iCommand – Touch iCommand - Touch In the "Temperature" screen the temperature of the system is graphically displayed. Fig. 12: "Temperature" screen In the "Air quantity" screen the air quantity is displayed in cubic feet per hour. Fig. 13: "Air quantity" screen In the "Usage" screen the amount of operating hours, on-load hours, off-load hours and ready hours are graphically displayed. Fig.
iCommand – Touch iCommand - Touch Menu" screen The "Menu" button allows access to the menu system. All setting parameter are located here. Fig. 16: "Code input" screen Representation of the graphics The measured values for the pressure and the final compressor temperature are saved regularly. The collected data is graphically displayed. Within the graph surface the display area can be zoomed into by pulling on the rectangle using your fingers (Zoom iin). n).
iCommand – Touch iCommand - Touch 2.5 Switching the compressor on/off Switching the compressor on 1. Press . Switching the compressor off 1. Press . During the switch-off process, the compressor initially switches to "Off load" (motor running, however the compressor is not compressing any air; a flashing dot appears on the screen) for the duration of the off time. Only then does the compressor switch off (the motor stops). 2.6 Access to the menu system 2.6.
iCommand – Touch iCommand - Touch 2.6.2 Access to the menu system without a code In the menus all changeable parameter can be selected via a button (see Fig. 19). Fig. 19: "Main menu" screen When accessing the menu system without a code only a value in the display is released. Instead of a button, a light blue field (Fig. 20) appears. The main menu includes the following submenus: Control Operating parameters Fig.
iCommand – Touch iCommand - Touch 2.6.3 Access to the menu system code 1 Parameter input When accessing the menu system with code "1" settings are available in the controller. If a code is entered, all values are highlighted in white (Fig. 21) and can be changed by selection on the individual buttons. For example, if the "Cut-out pressure" button is selected in the "Control" screen, then the submenu is reached (Fig. 22), in which the stop pressure can be set. Fig.
iCommand – Touch iCommand - Touch 2.7 Menu system Overview The main menu includes the following submenus: Control ( Chapter 2.7.1 ‘"Control" menu’ on page 30) Operating parameters ( Chapter 1.5 ‘Environmental protection’ on page 32) Maintenance / counter ( Chapter 2.7.3 ‘"Maintenance / counter" menu ’ on page 34) Fig. 23: "Main menu" screen Timer ( Chapter 1.
iCommand – Touch iCommand - Touch 2.7.1 "Control" menu This menu contains the following parameter: Parameter Value setting/Initial setting/Remarks Compressor type State Start-up pressure Lower limit for the pressure regulation. All Editable All Editable All Editable All Editable All (only during LLC operation) Editable Setting range: 51 PSI – Stop pressure minus 1 PSI Initial setting: depending on compressor type Cut-out pressure Upper limit for the pressure regulation.
iCommand – Touch iCommand - Touch 2.7.2 "Operating parameters" menu This menu contains the following parameters: Parameter Value setting/Initial setting/Remarks Compressor type State Automatic restart Automatic restart after power failure. All Editable All Editable All Editable All Editable All Editable All Editable Setting range: Yes/No Initial setting: No Remote On/Off Specifies the possibility to switch the system on or off remotely.
iCommand – Touch iCommand - Touch Parameter Value setting/Initial setting/Remarks Compressor type State Max. no. of motor starts During activated switch cycles monitoring: maximum amount of permitted motor starts per hour. All Editable All Editable Setting range: 1 – 60 /h Initial setting: depends on compressor type Lead lag control During operation with an external LLC (as LLC slave) Local pressure tolerance is ignored. However, maximum pressure is still monitored.
iCommand – Touch iCommand - Touch 2.7.3 2.7.3.1 "Maintenance / counter" menu Maintenance intervals This menu contains the following parameters: Parameter Value setting/Initial setting/Remarks Compressor type State Suction filter maintenance interval Time interval in which the suction filter should be serviced. All Display Oil/oil filter maintenance interval Time interval in which the oil or oil filter should be serviced.
iCommand – Touch iCommand - Touch 2.7.3.
iCommand – Touch iCommand - Touch 2.7.4 "Timer" menu Overview Date/Time ( Chapter 2.7.4.1 ‘Date/Time screen’ on page 36) Switching times compr. ( Chapter 2.7.4.2 ‘"Switching times compr." screen’ on page 36) Pressure times compr. ( Chapter 2.7.4.3 ‘"Pressure times compr." screen’ on page 37) Fig. 24: "Timer" screen 2.7.4.1 Switching times outputs ( Chapter 2.7.4.4 ‘"Switching times outputs" screen ’ on page 38) Date/Time screen This menu is used to set time and date.
iCommand – Touch iCommand - Touch In the displayed example (Fig. 27) the compressor would operate at least from Monday to Friday from 1 pm to 10:30 pm. To switch the compressor on for one or several days continuously, the respective days must be selected and 00:00 must be entered for switching times. Fig. 27: "Switching times compr." screen for Channel 1 2.7.4.3 "Pressure times compr." screen The timer can be activated and deactivated.
iCommand – Touch iCommand - Touch 2.7.4.4 "Switching times outputs" screen Programming of the time schedule for the digital outputs is done analogous to the Switching times compressor. There are four schedules available. These can be allocated to the digital outputs if required. Via the "Timer Scheme 1" (Fig. 30/1) the channel overview for scheme 1 can be accessed. Fig. 30: "Switching times outputs" screen This channel overview shows that Channel 1 is presently active.
iCommand – Touch iCommand - Touch 2.7.4.5 "Dimensions / Offset" screen The pressure dimension, temperature dimension, volume and pressure offset can be set in the "Dimensions / Offset" screen. Fig. 34: "Dimensions / Offset" screen Parameter Value setting/Initial setting/Remarks Compressor type State Pressure dimension Display unit for all pressure values.
iCommand – Touch iCommand - Touch 2.7.4.6 "Diagrams" screen Settings for the illustration of the diagrams can be made in the "Diagrams" screen. Fig. 35: "Diagrams" screen Parameter Value setting/Initial setting/Remarks Compressor type State Storage interval Specifies the recording interval for the flow diagrams.
iCommand – Touch iCommand - Touch Parameter Value setting/Initial setting/Remarks Compressor type State All Editable All Editable ture flow diagram. Setting range: Temperature graph low – 302 °F Initial setting: 212 °F Air flow Y-axis low Specifies the lower limit of the Y-axis after actuating the double arrow button (Y-restore) in the volume flow diagram.
iCommand – Touch iCommand - Touch 2.7.4.8 "Screensaver" screen In this menu the settings for the screensaver can be performed. Fig. 38: "Screensaver" screen Parameter Value setting/Initial setting/Remarks Compressor type State Screensaver active Specifies if the Screensaver function is active. Should the screensaver be active, the screensaver will be shown after the delay and dimmed to "Brightness screensaver". A touch to the screen on any place will activate the screensaver.
iCommand – Touch iCommand - Touch 2.7.4.9 "Lock Display" screen This function is used to clean the display without accidental triggering operation. After this function has been started, the control cannot be used for one minute. This function is available regardless of code level. Fig. 39: "Lock Display" screen 2.7.5 "Configuration" menu Overview This menu contains the following submenus: Communication ( Chapter 0 ‘"Communication" screen’ on page 44) MK200 modules ( Chapter 2.7.5.
iCommand – Touch iCommand - Touch Parameter Value setting/Initial setting/Remarks Compressor type State RS485 protocol Specifies the protocol type on the RS485 networking interface. All Display All Display All Display All Display All Display Setting range: MODBUS / Standard RS485 address Specifies the participants address in the RS485 network.
iCommand – Touch iCommand - Touch 2.7.5.1 "MK200 modules" screen Overview Different MK200 modules can be connected to the RS485 bus. Here, each model must have its own address and each address must only occur once. In principle 32 participants are possible. Whether the ICOMMAND - TOUCH establishes a communication to a module and monitors a fault of a module depends on the settings in this menu. Fig.
iCommand – Touch iCommand - Touch 2.7.5.2 "Inputs / Outputs" screen Overview This menu is used to assign functions to the ICommand - Touch P digital inputs and outputs and to the accessory modules. Fig. 43: "Inputs ICommand - Touch" screen (Part 1/2) Eight digital inputs and seven digital outputs are available on the ICommand - Touch P. These are preconfigured for the initial setting; however it is possible to change if required.
iCommand – Touch iCommand - Touch Parameter Value setting/Initial setting/Remarks Compressor type State All Display All Display All Display All Display All Display All Display Setting range: Yes/No Initial setting: No Starting temp. heating Specifies the switch-on temperature for the heating system (programmable output). Setting range: 36 °F – Shut-down temp. heating Initial setting: 36 °F Shut-down temp.
iCommand – Touch iCommand - Touch 2.7.5.3 "Compressor type" screen This menu shows the settings for the compressor type. Fig. 46: "Compressor type" screen Parameter Value setting/Initial setting/Remarks Compressor type State Main type Specifies the compressor family for further compressor selection. All Display Compressor selection Specifies the compressor. Caution! When changing this parameter the type-specific parameters are set to their initial setting.
iCommand – Touch iCommand - Touch 2.7.6 "Factory settings" menu In the "Factory settings" menu the operating times and final compressor temperature are displayed. Fig. 47: "Factory settings" screen Parameter Value setting/Initial setting/Remarks Compressor type State Start-up time Specifies the start-up time of the motor.
iCommand – Touch iCommand - Touch 2.7.7 "Fault log" menu The last 20 messages are stored in the message memory. Here, the / ) newest messages appear first. Using the arrow buttons ( scroll to older messages. For each entry the following information is available: Entry number Warning or fault symbol Fig. 48: "Messages" menu for massages, Time the message cause appeared faults and maintenance Message in plain text Currently still waiting - meaning not confirmed messages - are shown flashing.
iCommand – Touch iCommand - Touch Individual settings (e.g. switch-on times, switch-off and change intervals) can be set in the "LLC configuration" (Fig. 50) screen. Fig. 51: "LLC configuration" screen (Part 1/2) Using the button the second part of the menu can be screen (Fig. 52) accessed. Fig.
iCommand – Touch iCommand - Touch Parameter Value setting/Initial setting/Remarks Compressor type State All Editable All Editable All Editable All Editable All Editable significantly exceeded. Setting range: Yes/No Initial setting: No Remote LLC Specifies if the switching off for all the LLC masters and connected slaves is possible via the ACP controlled compressor stage.
iCommand – Touch iCommand - Touch Parameter Value setting/Initial setting/Remarks Compressor type State Act. damping initial Specifies the minimum time of the first switch-on of a compressor. All Editable All Editable All Editable All Editable All Editable All Editable All Editable Setting range: 0 – 600 s Initial setting: 5s Deact. damping initial Specifies the minimum time of the first switch-off of a compressor. Setting range: 0 – 60 s Initial setting: 2 s Act.
iCommand – Touch iCommand - Touch 2.7.9.1 "LLC priorities" screen This menu contains the settings for the priority assignments of the individual compressors. The values set here only apply if no timer channel of the timer LLC priorities is active. Fig. 53: "LLC priorities" screen Parameter Value setting/Initial setting/Remarks Compressor type State Priority compressor 1 – 5 Specifies a priority level for each compressor in the LLC series.
iCommand – Touch iCommand - Touch 2.7.9.3 "Pressure times LLC" screen The pressure times of the LLC are defined in this menu (increase/decrease). This only applies for the LLC master. Programming is done analogous to the "Pressure times compr." in section Chapter 2.7.4.3 ‘"Pressure times compr." screen’ on page 37. Fig. 55: "Pressure times LLC" screen 2.7.9.4 "Priority LLC" screen The switch-on/off times of the priority switching of the LLC are defined in this menu.
iCommand – Touch iCommand - Touch 2.7.10 "SD - Card" menu All functions with access to the SD - Card are located in this menu. The respective card must be inserted for usage. 2.7.10.1 Save parameters The current parameter set is written on the SD - Card. Insert a SD Card without write protection. 2.7.10.2 Load parameters The parameter set of SD - Cards can be read with this function. The SD - Card with the "ACPParam.par" must be inserted.
iCommand – Touch iCommand - Touch 2.8 Messages 2.8.1 Overview A flashing warning triangle (Warning/Maintenance) or a tool symbol (Fault) (Fig. 59/1) will appear in the left top of the basic display, if a new message is present. In addition a message pop-up appears at the bottom of the display the message in plain text (Fig. 59/2). The message window can be closed with the quit button (Fig. 59/3).
iCommand – Touch iCommand - Touch Warning message Remarks Compressor type W033: Speed reduction The on "W034: "Speed reduction" programmed digital input was opened. Delay 1 s. All W034: Dryer The on "W034: Dryer" programmed digital input was opened.- no delay. All W036: Condensate drain The on "W036: "Condensate drain" programmed digital input was closed. All W037: Air filter The on "W037: "Air filter" programmed digital input was closed. Monitoring starts after 15 minutes.
iCommand – Touch iCommand - Touch Warning message Remarks Compressor type W055: Access SD-Card During the access to the SD - Card a fault occurred. All W056: Ext. War. 1 The on W056: Ext. maint. 1 programmed digital input was opened. All W057: Ext. War. 2 The on W057: Ext. War. 2 programmed digital input was opened. All W058: Ext. War. 3 The on W058: Ext. War. 3 programmed digital input was opened. All W059: Ext. War. 4 The on W059: Ext. War. 4 programmed digital input was opened.
iCommand – Touch iCommand - Touch 2.8.3 Fault messages A flashing tool symbol will appear in the left top of the basic display, if a fault message is present. In addition a message pop-up appears at the bottom of the display the message in plain text . The message window can be closed with the quit button. The fault icon in the title psi stays but only until the cause of the error has been corrected. The compressor is switched-off.
iCommand – Touch iCommand - Touch Fault message Remarks Compressor type E078: Line pressure high Network pressure too high. The pressure has exceeded the set upper limit. All E079: System pressure conf. The system pressure switch digital input has not opened after 35 s in on-load operation. All E095: I/O-Module (Add.4) The accessory module on address 4 (Type MK200 8E4RA) does not respond. This monitoring is only active, if this module has been selected. All E096: I/O-Module (Add.
iCommand – Touch iCommand - Touch 2.8.4 Maintenance messages A flashing warning triangle will appear in the left top of the basic display, if a new maintenance warning is present. In addition a message pop-up appears at the bottom of the display the message in plain text. The message window can be closed with the quit button. The warning triangle in the title psi stays but only until the maintenance has been confirmed. The compressor continuous to run.
iCommand – Touch Index 3 Index A E Air Control controller AC P Brief description .............................................. 11 Emergency stop button .......................................... 8 Environmental protection Code input ....................................................... 21 Coolant liquid...................................................... 8 Display structure ............................................. 13 Lubricants ...........................................................