36
Full
E406: Process A164-<x>-<y> died while initializing
Cause:
Process A164-<x>-<y> was deleted during its initialization.
Effect:
If <y> equals C: Communication to all devices configured for this port will be unavailable.
If <y> equals P: No polling of devices will occur for this port. Demand scanning is
available.
Remedy:
Address any fatal or non-fatal error message preceding this message.
Call the Customer Service Department and report this error.
E407: Error <x> signalling A164-<y>-<z> process
Cause:
The BECO2200 DCA was unable to signal the A164-<y>-<z> process. The error code
returned was <x>.
Effect:
If <y> equals C: Communication to all devices configured for this port will be unavailable.
If <y> equals P: No polling of devices will occur for this port. Demand scanning is
available.
Remedy:
Call the Customer Service Department and report this error.
E408: Unable to allocate polling list
Cause:
The BECO2200 DCA was unable to allocate enough memory for is polling lists.
Effect:
The BECO2200 DCA will be unable to poll any of the devices configured. Demand scanning
is available.
Remedy:
Reduce the amount of RAM used by this and any other application in the system. The
parameters that affect the amount of RAM required by this application are noted in their
associated chapters.
Upgrade the GE Energy Services product to a model with more memory.
Call the Customer Service department and report this error.
E409: Error <x>, invalid start signal from Spawner
Cause:
This process failed to receive the start signal from the BECO2200 DCA spawner. The error
code returned was <x>.