Technical Manual

Each line displays a maintenance item that has
been set up via GenLink. The value displayed is the
approximate % of life remaining before maintenance
should be performed. Refer to the Maintenance setup
using GenLink.
Press the “ENTER” button.
This is a typical third Maintenance Status page. Each
line displays a maintenance item that has been set
up via GenLink. The value displayed is the approxi-
mate % of life remaining before maintenance should
be performed. Refer to the Maintenance setup using
GenLink.
Press the “ENTER” button.
This is a typical fourth Maintenance Status page. The
first line is the display contrast. The display contrast
is able to be changed on this page. However, changing
this setting can result in the display becoming non-
readable. Use caution. Use the arrow buttons to go to
the contrast field. Press the “ENTER” button to enter
edit mode. Use the arrow buttons to change the con-
trast value (range is 00 to 37). Pressing the “HOME”
button while in edit mode will return the value to the
last entered value. Press the “ENTER” button to exit
edit mode.
GENERATOR
There are three Generator Parameter pages – voltage
parameters, power parameters, and i2t parameters.
Do the following to view the generator parameter
pages:
Press the “MENU” button.
Press the button and then the button.
Press the “ENTER” button.
This is a typical first Generator Parameter page for a
three phase system.
LINE 1: Phase titles for the voltage and current.
LINE 2: Line-to-Line voltages in Volts RMS.
LINE 3: Line currents in Amps RMS.
LINE 4: Generator frequency in Hz followed by the
“More” field to allow page selection.
The voltages can be converted to values representing
the line-to-neutral voltages by changing the title line
(first line) using edit mode. Use the arrow buttons
to move to one of the title fields – A-B, B-C, or C-A.
Press the “ENTER” button to enter edit mode. Use
the up or down arrow button to change the display to
A-N, B-N, and C-N. Press the “ENTER” button to exit
edit mode. The same process is followed to return to
line-to-line displays. This also affects the left display
voltage page.
18
General Information
H-100 Control Panel Technical Manual