Technical Manual

27
Select the time of day to run exercise.
Verify “QuietTest®” is not checked. Press “Apply”.
Setup of Normal exercise is now complete. For this
example, exercise will start every Wednesday at 10:30
AM and run until about 10:50 AM
If exercise of the HTS is desired, Click on “Transfer
on exercise” to enable transferring of the load to the
generator during exercise.
NOTE:
This feature is only available in non-QuietTest®
exercise and when an HTS is in the system.
QUIETTEST
®
SETUP USING FRONT
PANEL
Press the “MENU” button.
Move the cursor using the arrow keys to the Exercise/
HTS menu item.
Press the “ENTER” button.
Move the cursor to the “Exercise Enabled” field on
the first line.
Press the “ENTER” button to enter edit mode.
General Information