Technical Manual

H-100 DIGITAL OUTPUT FUNCTIONS
Number Default Function Name Function Description
1 COMMON ALARM An alarm is active
2 COMMON WARNING A warning is active
3 GEN RUNNING Generator is running
4 ALARMS ENABLED All alarm hold off delays have expired, so all alarms are enabled
5 READY FOR LOAD Generator is warmed up and ready to accept power loading
6 GEN READY TO RUN Generator is ready to start
7 GEN STOPPED-ALRM Generator stopped due to a shutdown alarm
8 GEN STOPPED Generator is stopped
9 GEN IN MANUAL Generator in MANUAL mode ( key switch in MANUAL or ILC overriden)
10 GEN IN AUTO Generator in AUTO mode ( key switch in AUTO or ILC overriden )
11 GEN IN OFF Generator in OFF mode ( key switch in OFF or ILC overriden )
12 OVERCRANK ALARM Generator has unsuccessfully tried to start the designated number of times
13 OIL INHIBIT ALRM Oil pressure too high for a stopped engine
14 ANNUNC SPR LIGHT ILC controlled: this function operates the spare remote annunciator light
15 OIL TEMP HI ALRM Oil Temperature has gone above maximum alarm limit
16 OIL TEMP LO ALRM Oil Temperature has gone below minimum alarm limit
17 OIL TEMP HI WARN Oil Temperature has gone above maximum warning limit
18 OIL TEMP LO WARN Oil Temperature has gone below maximum warning limit
19 OIL TEMP FAULT Oil Temperature sensor exceeds nominal limits for valid sensor reading
20 COOL TMP HI ALRM Coolant Temperature has gone above maximum alarm limit
21 COOL TMP LO ALRM Coolant Temperature has gone below minimum alarm limit
22 COOL TMP HI WARN Coolant Temperature has gone above maximum warning limit
23 COOL TMP LO WARN Coolant Temperature has gone below maximum warning limit
24 COOL TMP FAULT Coolant Temperature sensor exceeds nominal limits for valid sensor reading
25 OIL PRES HI ALRM Oil Pressure has gone above maximum alarm limit
26 OIL PRES LO ALRM Oil Pressure has gone below minimum alarm limit
27 OIL PRES HI WARN Oil Pressure has gone above maximum warning limit
28 OIL PRES LO WARN Oil Pressure has gone below maximum warning limit
29 OIL PRES FAULT Oil Pressure sensor exceeds nominal limits for valid sensor reading
30 COOL LVL HI ALRM Coolant Level has gone above maximum alarm limit
31 COOL LVL LO ALRM Coolant Level has gone below minimum alarm limit
32 COOL LVL HI WARN Coolant Level has gone above maximum warning limit
33 COOL LVL LO WARN Coolant Level has gone below maximum warning limit
34 COOL LVL FAULT Coolant Level sensor exceeds nominal limits for valid sensor reading
35 ANALOG 5 HI ALRM Analog Input #5 has gone above maximum alarm limit
FUEL LVL HI ALRM Fuel Level
36 ANALOG 5 LO ALRM Analog Input #5 has gone below minimum alarm limit
FUEL LVL LO ALRM Fuel Level
37 ANALOG 5 HI WARN Analog Input #5 has gone above maximum warning limit
FUEL LVL HI WARN Fuel Level
38 ANALOG 5 LO WARN Analog Input #5 has gone below maximum warning limit
FUEL LVL LO WARN Fuel Level
39 ANALOG 5 FAULT Analog Input #5 sensor exceeds nominal limits for valid sensor reading
FUEL LVL FAULT Fuel Level
40 ANALOG 6 HI ALRM Analog Input #6 has gone above maximum alarm limit
FUEL PRS HI ALRM Fuel Pressure
INLT TMP HI ALRM Inlet Air Temperature
41 ANALOG 6 LO ALRM Analog Input #6 has gone below minimum alarm limit
FUEL PRS LO ALRM Fuel Pressure
INLT TMP LO ALRM Inlet Air Temperature
42