Technical Manual

43
Number Default Function Name Function Description
42 ANALOG 6 HI WARN Analog Input #6 has gone above maximum warning limit
FUEL PRS HI WARN Fuel Pressure
INLT TMP HI WARN Inlet Air Temperature
43 ANALOG 6 LO WARN Analog Input #6 has gone below maximum warning limit
FUEL PRS LO WARN Fuel Pressure
INLT TMP LO WARN Inlet Air Temperature
44 ANALOG 6 FAULT Analog Input #6 sensor exceeds nominal limits for valid sensor reading
FUEL PRS FAULT Fuel Pressure
INLT TMP FAULT Inlet Air Temperature
45 ANALOG 7 HI ALRM Analog Input #7 has gone above maximum alarm limit
GOV POS HI ALARM Throttle Position
46 ANALOG 7 LO ALRM Analog Input #7 has gone below minimum alarm limit
GOV POS LO ALARM Throttle Position
47 ANALOG 7 HI WARN Analog Input #7 has gone above maximum warning limit
GOV POS HI WARN Throttle Position
48 ANALOG 7 LO WARN Analog Input #7 has gone below maximum warning limit
GOV POS LO WARN Throttle Position
49 ANALOG 7 FAULT Analog Input #7 sensor exceeds nominal limits for valid sensor reading
GOV POS FAULT Throttle Position
50 ANALOG 8 HI ALRM Analog Input #8 has gone above maximum alarm limit
OXYGEN HI ALARM Emissions Sensor
FLUID BS HI ALRM Fluid Basin
51 ANALOG 8 LO ALRM Analog Input #8 has gone below minimum alarm limit
OXYGEN LO ALRM Emissions Sensor
FLUID BS LO ALRM Fluid Basin
52 ANALOG 8 HI WARN Analog Input #8 has gone above maximum warning limit
OXYGEN HI WARN Emissions Sensor
FLUID BS HI WARN Fluid Basin
53 ANALOG 8 LO WARN Analog Input #8 has gone below maximum warning limit
OXYGEN LO WARN Emissions Sensor
FLUID BS LO WARN Fluid Basin
54 ANALOG 8 FAULT Analog Input #8 sensor exceeds nominal limits for valid sensor reading
O2 SENSOR FAULT Emissions Sensor
FLUID BS FAULT Fluid Basin
55 ANALOG 9 HI ALRM Analog Input #9 has gone above maximum alarm limit
CHG CURR HI ALRM Battery Charge Current
56 ANALOG 9 LO ALRM Analog Input #9 has gone below minimum alarm limit
CHG CURR LO ALRM Battery Charge Current
57 ANALOG 9 HI WARN Analog Input #9 has gone above maximum warning limit
CHG CURR HI WARN Battery Charge Current
58 ANALOG 9 LO WARN Analog Input #9 has gone below maximum warning limit
CHG CURR LO WARN Battery Charge Current
59 ANALOG 9 FAULT Analog Input #9 sensor exceeds nominal limits for valid sensor reading
CHG CURR FAULT Battery Charge Current
60 BAT VOLT HI ALRM Battery Voltage has gone above maximum alarm limit
61 BAT VOLT LO ALRM Battery Voltage has gone below minimum alarm limit
62 BAT VOLT HI WARN Battery Voltage has gone above maximum warning limit
Appendix B
H-100 Control Panel Technical Manual