14 Owner’s Manual for 7.5 kW PowerPact™
5. To crank and start the engine, press the control
panel MANUAL button.
6. Allow the engine to stabilize and warm up for a few
minutes.
7. Set the main line circuit breaker (Generator
Disconnect) to ON or CLOSED. The standby
power source now powers the loads.
Figure 3-4. Manual Transfer Switch Operation
IMPORTANT NOTE: Actual switch operation may vary. Follow directions in the appropriate transfer switch manual.
Transfer Back to Utility Power Source
When utility power has been restored, transfer back to
utility source and shut down the generator. To manually
transfer back to utility power and shut down the
generator:
1. Set the Main Line Circuit Breaker (Generator
Disconnect) to OFF or OPEN.
2. Allow the engine to run for two minutes at no-load
to stabilize the internal temperatures.
3. Press the control panel OFF button. The engine
should shut down.
4. Verify that utility power supply to the transfer switch
is turned off.
5. Use the manual transfer handle inside the transfer
switch to move the main contacts back to the
UTILITY position (loads connected to the utility
power source, A in Figure 3-4).
6. Turn on the utility power supply to the transfer
switch using the means provided.
7. Press the control panel AUTO button.
Automatic Transfer Operation
To select automatic operation:
1. Make sure the transfer switch main contacts are
set to the UTILITY position (loads connected to the
utility power source).
2.
Verify that normal UTILITY power source voltage is
available to transfer switch terminal lugs N1 and N2.
3. Press the AUTO button on the control panel
interface.
4. Set the main circuit breaker (Generator
Disconnect) to the ON (Closed) position.
With these steps complete, the generator will start
automatically when utility source voltage drops below a
preset level. After the unit starts, loads are transferred to
the standby power source.
000947
A
B
MANUAL
Will not transfer to generator if utility is present.
Will transfer to generator if utility fails (below 65% of nominal for 10 consecutive seconds).
Will transfer back when utility returns for 15 consecutive seconds. The engine will continue to
run until removed from the MANUAL mode.
AUTO
Will start and run if utility fails (below 65% of nominal for five consecutive seconds).
Will start a six second engine warm-up timer (or 30 seconds; refer to Cold Smart Start).
Will not transfer if utility subsequently returns.
Will transfer to generator if utility is not present.
Will transfer back to utility once utility returns (above 80% of nominal) for 15 seconds.
Will not transfer back to utility unless utility returns. The generator will shut down if the OFF
button is pressed or a shutdown alarm is present.
Once utility power is returned, the generator will shut down after one minute cool-down time.
EXERCISE
Will not exercise if generator is already running in either AUTO or MANUAL mode.
During exercise, the control panel will only transfer if utility fails during exercise for six
seconds (or 30 seconds; refer to
Cold Smart Start) and will operate as normal in AUTO
mode.