Replacement Part List

4 of 5
Transfer Switch Features
Electrically operated, mechanically-held contacts for fast,
positive connections.
Rated for all classes of load, 100% equipment rated, both
inductive and resistive.
2-pole, 240 VAC contactors.
60 millisecond transfer time.
NEMA 1 (indoor rated) enclosure is standard.
Multi listed for use with 1" standard, tandem, GFCI and
AFCI breakers from Siemens, Murray, Eaton, and Square D
for the most flexible and cost effective install.
Flush mountable.
7.5 kW
®
transfer switch
PowerPact™ System - 7.5 kW
*Function of Controller
Model
G006998-1
No. of Poles 2
Current Rating (Amps) 50
Voltage 120/240 1Ø
Utility Voltage Monitor (Fixed)*
—Pick-up
Dropout
80%
65%
Return to Utility* approx. 15 sec
Exerciser weekly for 12 minutes* Standard
UL Listed Standard
Total of Pre-wired Circuits
No. 15 A 120 V
No. 20 A 120 V
No. 20 A 240 V
No. 30 A 240 V
No. 40 A 240 V
No. 50 A 240 V
8
5
1
-
1
-
-
Tandem Breaker Capability 8 spaces
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 240 Vols
10,000
Weight (Lb/Kg) 20/9.1
Installation whips included No
Dimensions
Mechanical Dimensions
Height Width
Depth
H1 H2 W1 W2
in 11.5 14.8 11 14.4 4
mm 292 375 280 366 100
Wire Ranges
Neutral Lug Ground Lug
2/0 - #14 2/0 - #14
H1
W1
D
W2
H2