PWRview Installation with Two ATS

PWRview Installation with Two Automatic Transfer Switches 1
INSTRUCTION SHEET
PWRview™ Installation with Two
Automatic Transfer Switches
Intended for Installation of the PWRview
Automatic Transfer Switch (ATS), model
RXEMW200A3, and an additional,
non-PWRview ATS.
Installation Process
1. Install each ATS per typical installation as outlined
in the ATS manual.
2. Ensure that T1 and T2 from each ATS are on the
same voltage phase.
3. Attach CT’s from UCT2 in ATS 2; label the leads
T1 and T2.
4. Take the extensions from SCTE2 and label them
T1 and T2.
5. Route the extensions from ATS 2 to ATS 1 and
connect them to the corresponding CT’s in ATS 2.
6. Attach CT’s shipped with ATS1 in ATS1; label the
leads T1 and T2.
7. Take the y-splitters from SYCOM2 and label them
T1 and T2.
8. Inside ATS1, connect the CT leads from both ATS1
and ATS2 to the corresponding y-splitters.
9. Install y-splitters at the PWRview meter in ATS1 to
CT ports 1 (T1) and 2 (T2).
10. Complete the PWRview meter install as outlined in
ATS 1’s installation.
Table 1 - Equipment Needed
Part Number Description
- 1 x view 200A ATS [ATS 1]
-
1 x non-PWRview ATS (100, 150, or
200A) [ATS 2]
UCT2 1 x Universal Current Transformer Kit
SYCOM2 1 x Y-Splitter
SCTE2
1 x Extension Cable 10’ length, add as
needed
(000191)
DANGER
Automatic start-up. Disconnect utility power and
render unit inoperable before working on unit.
Failure to do so will result in death or serious injury.
(000187)
WARNING
Electrocution. Potentially lethal voltages are generated
by this equipment. Render the equipment safe before
attempting repairs or maintenance. Failure to do so
could result in death or serious injury.
(000100a)
Consult Manual. Read and understand manual
completely before using product. Failure to
completely understand manual and product
could result in death or serious injury.
WARNING
(000182a)
WARNING
Equipment damage. Only qualified service personnel may
install, operate, and maintain this equipment. Failure to
follow proper installation requirements could result in death,
serious injury, and equipment or property damage.

Summary of content (2 pages)