Specification

Acoustic Ceiling Products (ACP) – Genesis Ceiling Panels Section 09 51 01
August 7, 2012 PVC CEILING PANELS
[Project Identification] Page 4
3.2 INSTALLATION
A. Install assembly in accordance with manufacturer's instructions and as supplemented in
this section.
Include the first paragraph below if a reflected ceiling plan is not included with the drawings; or the
subsequent paragraph if a reflected ceiling plan is included.
B. Lay out assembly to a balanced grid design with edge units no less than 50 percent of
acoustic unit size.
[OR]
C. Locate assembly on room axis according to reflected ceiling plan.
D. Cutting Panels: Using a utility knife and straight edge, score the finish side of the panel.
Bend panel at the score mark and snap apart.
Edit the following paragraph and sub-paragraph. Panels will be laid-in.
E. T-bar Panel Mount:
1. If grid covers are used, install them prior to installing panels. Refer to GridMax
installation instructions.
2. Install border panels, then full panels working across the ceiling area.
3. To cut panels, measure distance between t-bar centers, or between the t-bar center
and closest edge of wall molding.
4. If hold-down clips are used, reach over the installed panel and snap over grid
members.
F. Perimeter Molding:
1. Install edge molding at intersection of ceiling and vertical surfaces into bead of
acoustic sealant that is not visible after installation.
2. Use single piece longest practical lengths.
3. Miter corners.
3.3 SCHEDULE
Provide a schedule when various ceiling locations, ceiling assembly types, acoustic unit designs, or other
variables require listing for clarity. Use a table if there are numerous varieties. The following are
examples to illustrate a scheduled item:
END OF SECTION