Use and Care Manual

FIGURE 7
WIRING/GENERAL (7139CS ONLY)
1. Use ANSI/UL listed cable with Class 1 insulation.
2. Observe local code requirements. Use box connector to anchor cable to outlet box.
3. Metal outlet boxes must be grounded to earth ground.
4. NOTICE: USE ONLY DURACELL® MN 1604 BATTERY WITH THE 7139CS SERIES
SMOKE ALARMS. AVAILABLE AT MANY RETAIL STORES.
CAUTION: Turn off electricity to prevent SHOCK and damage to smoke alarm. Be sure the
power line to device is not controlled by any on/off switch, or other type of switch, other than
a fuse or circuit breaker.
IMPORTANT: Insure that all fluorescent lighting fixtures are properly grounded or on
separate circuits.
NOTICE: THE WIRING TO BE USED SHALL BE IN ACCORDANCE WITH THE
PROVISIONS OF ARTICLE 210 OF THE NATIONAL ELECTRICAL CODE, NFPA 70. WIRE
INSTALLATION SHOULD BE PERFORMED ONLY BY A LICENSED ELECTRICIAN.
MOUNTING OUTLET BOX (7139CS ONLY)
Use a 2" x 3" switch box or a 4" square or octagon junction box. Mount a box for each
smoke alarm. If wall mounting is desired, be sure the box screws are oriented to upper right
and lower left corners. Be sure to use supplied mounting plate.
NOTICE: FOR TROUBLE AREAS WHERE THERE CAN BE A LARGE VOLUME OF AIR
BLOWING OUT THROUGH THE ELECTRICAL JUNCTION BOX. YOU MUST FIRST
ATTACH AN ADHESIVE BACKED FOAM GASKET, WHICH HAS BEEN PACKED WITH
YOUR SMOKE ALARM, TO THE BACK SIDE OF THE MOUNTING BRACKET BEFORE
IT'S SECURED TO THE JUNCTION BOX.
WIRING ONE SMOKE ALARM (7139CS ONLY)
1. Run a minimum of 16 gauge, 2-conductor cable, plus ground (3 wires) to the device
junction box from a power supply. Smoke alarms should be run on their own dedicated
circuit. Use ANSI/UL listed Class 1 wire.
NOTICE: THE WIRING TO BE USED SHALL BE IN ACCORDANCE WITH THE
PROVISIONS OF ARTICLE 300.3(B) OF THE NATIONAL ELECTRICAL CODE, NFPA 70,
AS WELL AS ARTICLE 210.
2. Make wire connections to the supplied plug-in connector as follows: black to black, white
to white, and connect the ground wire to the metal outlet box.
WHERE SMOKE ALARMS SHOULD BE PUT IN MOBILE HOMES
In mobile homes built after about 1978 that were designed and insulated to be energy-
efficient, smoke alarms should be installed as described in the section above. In older mobile
homes that have little or no insulation compared to today's standards, uninsulated metal
outside walls and roofs can transfer heat and cold from outdoors, making the air right next to
them hotter or colder than the rest of the inside air. These layers of hotter or colder air can
prevent smoke from reaching a smoke alarm. Therefore, put smoke alarms in such units
only on inside walls, not more than 12 inches (30 cm) from the ceiling. If you are not sure
about the insulation level in your mobile home, or if you notice that the walls or ceiling are
unusually hot or cold, put the smoke alarm on an inside wall.
Minimum protection requires one smoke alarm as close to the sleeping area as possible.
For better protection, put one smoke alarm in each room, but first read the "LOCATIONS TO
AVOID."
LOCATIONS TO AVOID
This smoke alarm must be installed within 16 feet of the pillow
Any location outside of 16 feet will cause this alarm to be less effective and not meet
code requirements.
Nuisance alarms are caused by placing smoke alarms where they will not operate
properly. To avoid nuisance alarms, do not place smoke alarms:
w In or near areas where combustion particles are normally present such as kitchens;
in garages where there are particles of combustion in vehicle exhausts; near furnaces,
hot water heaters, or gas space heaters. Install smoke alarms at least 20 feet
(6 meters) away from kitchens and other areas where combustion particles are
normally present.
w In air streams passing by kitchens. FIGURE 7 shows how a smoke alarm can be
exposed to combustion particles in normal air movement paths, and how to correct this
situation.
w In damp or very humid areas, or next to bathrooms with showers. The moisture
in humid air can enter sensing chamber as water vapor, then cool and condense
into droplets that cause a nuisance alarm. Install smoke alarms at least 10 feet
(3 meters) away from bathrooms.
w In very cold or very hot environments, or in unheated buildings or outdoor
rooms, where the temperature can go below or above the operating range of the
device. Temperature limits for proper operation are 40° to 100°F (4.4° to 37.8°C).
w In very dusty or dirty areas. Dust and dirt can build up on the smoke alarm's
sensing chamber and can make it overly sensitive, or block openings to the
sensing chamber and keep the smoke alarm from sensing smoke.
w Near fresh air inlets or returns or excessively drafty areas. Air conditioners,
heaters, fans, and fresh air intakes and returns can drive smoke away from smoke
alarms, making the devices less effective.
w In dead air spaces at the top of a peaked roof or in the corners between ceilings
and walls. Dead air may prevent smoke from reaching a smoke alarm.
w In insect-infested areas. If insects enter a smoke alarm's sensing chamber, they may
cause a nuisance alarm. Get rid of bugs before installing devices where bugs are a
problem.
w Near fluorescent light fixtures. Electrical "noise" from nearby fluorescent light fixtures
may cause a nuisance alarm. Install smoke alarms and fluorescent lights on
separate electrical circuits.
Never remove power from smoke alarm to silence a nuisance
alarm. Open a window or fan air around device to remove the smoke. The smoke
alarm will automatically turn off when the smoke in the air is completely gone. Do not
stand close to device. The sound produced by the smoke alarm is loud because it is
designed to awaken you in an emergency. Prolonged exposure to the horn at a close
distance may be harmful to your hearing.
NOTICE: RED-YELLOW WIRE: THE RED-YELLOW WIRE FROM THE SMOKE ALARM IS
FOR TANDEM CONNECTION ONLY. DO NOT USE, AND DO NOT REMOVE INSULATION
CAP UNLESS CONNECTING ANOTHER SMOKE ALARM.
}
SMOKE ALARM
HOT
NEUTRAL
TANDEM
BLACK
WHITE
GRAY
RED/
YELLOW
YELLOW
ORANGE
BLUE
BROWN
BROWN
AUXILARY
CONTACTS
INTERNAL
JUMPER
OPTIONAL STROBE
ACTIVATION
SMOKE ALARM
POWER
TANDEM
HOT
NEUTRAL
EXTERNAL RELAY
ACTIVATES
S
MOKE ALARM
STROBE ONLY
B
L
A
C
K
WHITE
RED/YELLOW
GRAY
120 VAC
7139CS WIRING
RELAY CONTACTS
RATED LOAD RESISTIVE
0.6 AMP at 125 VAC (MAX.)
OR 1 AMP at 24 VDC (MAX.)
1
11
2
10
4
9
3
5
6
TO EXISTING
SIGNALING CIRCUIT
STROBE ACTIVATION FROM
EXTERNAL SOURCE
550-0646
Page 4
WIRING TWO OR MORE SMOKE ALARMS (7139CS ONLY)
Tandem Installation
NOTICE: ALL SMOKE ALARMS IN TANDEM INSTALLATION MUST BE CONTROLLED
BY THE SAME FUSE OR CIRCUIT BREAKER. OTHERWISE TANDEM UNITS WILL NOT
OPERATE. TANDEM WILL OPERATE IN THE EVENT OF AC POWER FAILURE IF
BATTERY IS CONNECTED TO THE SMOKE ALARM.
LIMITATIONS: A maximum of six (6) smoke alarms of model 7139CS or models with the
relay option (F, HF, TF) may be tandem interconnected. Do not exceed 1125 feet between
first and last smoke alarm.
Wire used for interconnecting shall be in accordance with the latest edition of Article 760
of the National Electrical Code (NEC) and NFPA 70, and must not exceed a resistance of
10 ohms.