Specification

120 VOLTS
60 HZ
RED / YEL
WHT
BLK
SUPERVISION
WIRES
ACCESS
CONT
ACTS
ALARM
CONT
ACTS
TANDEM
POWER
CAUTION:
RED/YELLOW wire to be capped
when not in use. This wire is for
tandem connection only. Do not
connect to any other circuit.
9000/9003 Series Wiring Diagrams
ELECTRICAL
BOX
QUICK
DISCONNECT
TYPE PLUG
SMOKE
ALARM
1
2
3
TANDEM WIRE
NEUT
HOT
TO ADDITIONAL
GENTEX SMOKE ALARMS
LIMITATIONS:
Maximum of 12 alarms
(9120/9123, 9120/9123T,
9120/9123H, 9220/9223,
9220/9223T, 9220/9223H)
may be connected together.
Do not exceed 125 feet
between each detector. Do
not exceed 1125 feet
between the first and last
alarm. NOTE: Gentex smoke
alarms can not be intercon-
nected to detectors from
other manufacturers.
A MAXIMUM OF SIX (6)
ALARMS WITH A RELAY
MAY BE TANDEM
INTERCONNECTED.
(9120/9123F, 9120/9123TF,
9120/9123HF, 9220/9223F,
9220/9223TF, 9220/9223HF)
Tandem Wiring Diagram
Relay Models
GRA
Y
GRA
Y
YEL
ORN
BLU
VIO
VIO/BLK
RED/YEL
BLK
WHT
RELA
Y
CONT
ACTS
RATED LOAD RESISTIVE
1.0 AMP @ 24 VDC
0.6
AMP
@ 125 V
AC MAX
0.3 AMP @ 220 VAC MAX
Models
9120/9123F
9120/9123TF
9230/9223F
9220/9223TF
Isolated Thermal with
Optional Accessory Contacts
HF ONLY
SMOKE
ALARM
HEA
T
SENSOR
ACCESS
CONTACTS
ALARM
CONTACTS
TANDEM
POWER
SMOKE
ALARM
SMOKE
ALARM
1
2
3
1
2
3
ELECTRICAL
BOX
ELECTRICAL
BOX
Models
9120/9123H
9120/9123HF
9220/9223H
9220/9223HF
BRN
BRN
GREY
GREY
YEL
ORN
BLU
VIO
VIO/BLK
RED/YEL
BLK
WHT