Spec Sheet

Gillette Generators, Inc.
2921 Thorne Dr. Elkhart, IN 46514 Ph: 574-264-9639 Fax: 574-262-1840 Web: www.gillettegenerators.com spc4-180810
3
COOLING SYSTEM
Type of System ................................ Pressurized, closed recovery
Coolant Pump ..................................... Pre-lubricated, self-sealing
Cooling Fan Type (no. of blades) ................................. Pusher (8)
Fan Diameter inches (mm) ........................................... 52" (1321)
Ambient Capacity of Radiator °F (°C) .......................... 125 (51.6)
Engine Jacket Coolant Capacity Gal (L) ...................... 11.0 (50.0)
Radiator Coolant Capacity Gal. (L) .............................. 46.7 (212)
Maximum Restriction of Cooling Air Intake
and discharge side of radiator in. H
2
0 (kpa) .................. 0.5 (.125)
Water Pump Capacity gpm (L/min) .............. ................ 174 (660)
Heat Reject Coolant: Btu/min (kw) .............. ........... 20,784 (364)
Low Radiator Coolant Level Shutdown………………...Standard
Note: Coolant temp. shut-down switch setting at 230°F (110°C) with 50/50
(water/antifreeze) mix.
AIR REQUIREMENTS
Combustion Air, cfm (m
3
/min) .................... ............... 788 (22.0)
Radiator Air Flow cfm (m
3
/min) ................... ........ 36,000 (1,019)
Heat Rejected to Ambient:
Engine: kw (btu/min) ............................. ............. 61.0 (3486)
Alternator: kw (btu/min) ........................ ................ 23 (1309)
EXHAUST SYSTEM
Exhaust Outlet Size .............................................................. (2) 5"
Max. Back Pressure, in. hg (KPA). ................................ 3.0 (10.2)
Exhaust Flow, at rated kw: cfm (m
3
/min) ..... ..... ……2366 (67.0)
Exhaust Temp., at rated kw: °F (ºC) ……………..….1350 (732)
Engines are EPA certified for Natural Gas.
Deep Sea 7420
The 7420 controller is an
auto start mains (utility)
failure module for single
gen-set applications. This
controller includes a backlit
LCD display which
continuously displays the
status of the engine and
generator at all times.
The 7420 controller will also monitor speed, frequency,
voltage, current, oil pressure, coolant temp., and fuel levels.
These modules have been designed to display warning and shut
down status. It also includes: (11) configurable inputs (8)
configurable outputs voltage monitoring mains (utility)
failure detection (250) event logs configurable timers
automatic shutdown or warning during fault detection remote
start (on load) engine preheat advanced metering capability
hour meter text LCD displays protected solid state outputs
test buttons for: stop/reset manual mode auto mode lamp
test start button power monitoring (kWh, kVAr, kVAh,
kVArh)
SOUND LEVELS MEASURED IN dB(A)
Open Level 2
Set Encl.
Level 2, Critical Silencer ......................... 94............ ........... 80
Level 3, Hospital Silencer ........................................ ........... 75
Note: Open sets (no enclosure) has (2) optional silencer system choices
due to unknown job-site applications. Level 2 enclosure has installed
critical silencer with upgrade to hospital silencer. Sound tests are
averaged from several test points and taken at 23 ft. (7 m) from source
of noise at normal operation.
DERATE GENERATOR FOR ALTITUDE
3% per 1000 ft.(305m) above 3000 ft. (914m) from sea level
DERATE GENERATOR FOR TEMPERATURE
2% per 10°F(5.6°C) above 104°F (40°C)
DIMENSIONS AND WEIGHTS
Open Level 2
Set Enclosure
Length in (cm) ......................... 168 (427) ..... ................ 210 (534)
Width in (cm) ........................... 82 (208) ...... ................. 82 (208)
Height in (cm) .......................... 90 (228) ...... ................ 100 (254)
3 Ø Net Weight lbs (kg) ........ 9425 (4275) ... .......... 11925 (5409)
3 Ø Ship Weight lbs (kg) ...... 9825 (4457) ... .......... 12325 (5591)
This controller includes expansion features including RS232,
RS484 (using MODBUS-RTU/TCP), direct USB connection
with PC, expansion optioned using DSENet for remote
annunciation and remote relay interfacing for a distance of up to
3300FT. The controller software is freely downloadable from
the internet and allows monitoring with direct USB cable, LAN,
or by internet via the built in web interface.
Further expansion is available by
adding the optional “WebNet“ gateway
interface module. This device will allow
comprehensive monitoring of the generator
via the cloud including identification,
location, and status. Some advantages of this
module include: reduced site visits and
maintenance costs remote fuel management
fault analysis asset tracking automatic
system alerts maximized system up-time.
APPLICATION AND ENGINEERING DATA FOR MODEL SP-3500-60 HZ
DEEP SEA 7420 DIGITAL MICROPROCESSOR CONTROLLER