Technical Publication

1
INDEX
SECTION 1. General Requirements for All Long Line Set Applications .............................. 2
SECTION 2. Outdoor Unit and Indoor Unit are at the Same Elevation ............................... 4
SECTION 3. Outdoor Unit is Above the Indoor Unit ............................................................ 5
SECTION 4. Outdoor Unit is Below the Indoor Unit ............................................................ 6
SECTION 5. Calculations - Tubing Equivalent Length, Tube Size and Refrigerant ............ 7
Before connecting tubing, read the outdoor unit installation manual. Pay particular
attention to all safety precautions.
This long line set application guideline applies to all AHRI listed R-410A air conditioner and heat pump split
system matches of nominal capacity 18,000 to 60,000 Btuh. This guideline will cover installation requirements
and additional accessories needed for split system installations where the line set exceeds 80 feet (24.4 m) in
actual length. The long line sets can have three different configurations (1) Outdoor unit and Indoor unit are at
the same level, (2) Outdoor unit is above the Indoor unit coil, (3) Outdoor unit is below the Indoor unit.
This guideline is meant to provide installation instructions based on most common long line set applications.
Installation variables may affect the system operation.
Contact Technical Services
for variations or applications outside those outlined in this document.
TP-107K
TECHNICAL PUBLICATION
TP-107K
Goodman Company, L.P.
April 2017
LONG LINE SET
APPLICATION R-410A