User Manual

64 GMC-I Messtechnik GmbH
Test Steps with Automatic Evaluation (R
ISO
, I
PE
)
The measured value is ascertained automatically within a speci-
fied period of time. The evaluation c
ycle is visualized as follows:
the progress bar starts at the left-hand edge of the display and
moves to the right. When it reaches the rightmost position, evalu-
ation has been completed. The test se
quence is then automati-
cally resumed.
Manual Evaluation of the Function Test
(prerequisite: “function test” sequence parameter is preset to “on”.
Evaluate the function test:
If you mark the function test as not passed with the
softkey shown at the right, the sequence is aborted and the
test is evaluated as not passed.
If
you evaluate the function test as passed, you can
simply continue with the test sequence.
In either case you can enter a comment, which can be
subsequently edited as well.
10.7 Setting Limit Values Manually
If “Expert” is selected instead of “Normal” in setup under “Auto
Measurements” in the “Limit Value Mode” submenu, the LIMIT
softkey appears next to the “measurement failed” popup. This key
makes it possible to enter a user-defined limit value (as a rule a
limit value specified by the manufacturer which deviates from the
standard):
10.8 Ending the Test Sequence
“Sequence finished” appears at the display.
Initial Display (memory screen)
Display of the memory screen depends on the setting in the setup
menu in the SETUP switch position:
Setup 1/3 > Auto. measurements > At end of sequence > Memor
y
screen.
If set to Results list,
the above display is skipped and the results list
shown below is displayed.
You can also access the results list by pressing the key
shown at the right.
Results List Display
Select the desired test step with the scroll keys.
If you want to view details for the selected test step, press
the magnifying glass+ key
.
Consideration of measuring error depen
ds on the setting in the
setup menu in the SETUP switch setting: Setup 1/3 > Auto. mea-
surements > Error considered. > Yes)
Display of Details for Individual Test Steps
The display is returned to the list of test steps by pressing
the magnifying glass– key
.
The memory screen is displayed again after acknowl-
edging the list.
10.9 Saving Test Results
Save the results of a successful test sequence by
pressing the Save key
.
or
Send measurement data to a PC (feature KD01),
via USB or
Bluetooth
®
(feature M01),
e. g. for storing in the IZYTRON .IQ report generating soft-
ware (push-print function), see IZYTRON .IQ online help for
description
Please observe the notes on saving data given in section 7.