Installation Guide

PIPING INSTALLATION
4. Properly align piping and tighten flare nut using a standard wrench and a torque wrench
as shown in figure to the below. Carefully tighten flare nuts to correct torque level referring
to the Torque Table above.
NOTE: Over tightening may damage flare connections and cause leaks.
5. Individually insulate each refrigerant line to prevent sweating.
Insulate pipes
Indoor Unit Piping
Taper Nut
Wrench
Torque Wrench
Piping
NOTE: For maximum serviceability, it is recommended to have refrigerant piping and
drain connections on the outside.
Refrigerant Piping Connections to Indoor Unit
1. Feed refrigerant pipes, drain hose and interconnecting wires assembly
through wall hole from outdoor to the indoor unit.
2. Adjust the length and carefully bend refrigerant pipes to meet indoor
unit refrigerant pipe connections with proper tools to avoid kinks.
3. Apply a small amount of refrigerant oil to the flare connection on
the refrigerant pipes.
22
Pipe Diameter Nut Size
Tightening Torque
inch (mm) inch (mm) ft-lbs N-m
1/4 (6.35) 1/4 (17) 10 to 13 14 to 18
3/8 (9.5) 3/8 (22) 25 to 30 34 to 42
1/2 (12.7) 1/2 (25) 36 to 45 49 to 61
5/8 (15.9) 5/8 (29) 50 to 60 68 to 82
Torque Table