Specification Sheet

3
Technical Data
November 2014
VAC-DT – MicroSet Dual Tech Low Voltage Vacancy Ceiling Sensor
www.coopercontrol.com
Wiring Diagrams
BLACK (COMMON)
BROWN (BLUE CONTROL)
YELLOW (CONTROL-OCC/DAY)
PURPLE (NORMALLY CLOSED)
GRAY (ISOLATED RELAY COMMON)
ORANGE (NORMALLY OPEN)
WHITE/BROWN (YELLOW CONTROL)
OAC AND VAC MANUAL MODE OPERATION:
1. SWITCHES ARE REQUIRED TO TURN
CORRESPONDING LOADS ON.
2. LOADS TURN OFF WHEN SENSOR
TIMES OUT OR WITH SWITCHES.
3. IF DAYLIGHT SENSOR IS ENABLED AND
LIGHT LEVEL IS ABOVE SETPOINT,
SWITCHPACK CONNECTED TO YELLOW
LEAD WILL NOT TURN LOAD ON.
OAC AUTOMATIC MODE OPERAT ION:
1. WHEN SENSOR ACTIVATES, BOTH
LOADS TURN ON.
2. SWITCHES CAN BE USED TO TURN
LOADS ON OR OFF.
3. IF DAYLIGHT SENSOR IS ENABLED AND
LIGHT LEVEL IS ABOVE SETPOINT,
SWITCHPACK CONNECTED TO YELLOW
LEAD WILL NOT TURN LOAD ON.
RECOMMENDED WIRE:
18-3 AWG STRANDED WIRE SHIELDED OR
NON/SHIELDED
BLUE (CONTROL-OCC)
RED (10-30 VDC)
LOAD "A"
BLUE
NEUTRAL
HOT
**USE BLACK LEAD FOR 120 VAC.
USE ORANGE LEAD FOR 277 VAC.
CAP UNUSED LEAD.
LINE
**HOT
WHITE
BLUE
SWITCH-
PACK
LOAD "B"
BLUE
NEUTRAL
HOT
**USE BLACK LEAD FOR 120 VAC.
USE ORANGE LEAD FOR 277 VAC.
CAP UNUSED LEAD.
LINE
**HOT
WHITE
BLUE
SWITCH-
PACK
BLACK (COMMON)
BLUE (CONTROL)
RED (15 VDC)
MODEL GMDS - LOAD "B"
(NORMALLY OPEN
MOMENTARY SWITCH)
MODEL GMDS - LOAD "A"
(NORMALLY OPEN
MOMENTARY SWITCH)
BLACK (COMMON)
BLUE (CONTROL)
RED (15 VDC)
NOTES
1. LOADS MAY BE ON SAME
CIRCUIT OR DIFFERENT
CIRCUITS OR VOLTAGES.
2. SP20-MV SWITCHPACK SHOWN.
120/277 VAC 20 AMP RATING.
VAC-DT-2000-R Model
*Wiring diagram for single sensor application.
Visit our website for other wiring diagrams.
Coverage
VAC-DT-1000-R
1,000 sq. ft.
VAC-DT-0501-R
500 sq. ft.
VAC-DT-2000-R
2,000 sq. ft.
8.5 ft
(2.59 m)
5 ft
(1.52 m)
10 ft
(3.05 m)
15 ft
(4.57 m)
23 ft
(7.01 m)
0
9 ft
(2.74 m)
9 ft
(2.74 m)
0
12 ft
(3.65 m)
12 ft
(3.65 m)
20 ft
(6.096m
)
20 ft
(6.096m
)
8.5 ft
(2.59 m)
17 ft
(5.18 m)
10 ft
(3 m)
5 ft
(1.5 m)
0
0
5 ft
(1.5 m)
10 ft
(3 m)
17 ft
(5.18 m)
23 ft
(7.01 m)
DT1k
9 ft
(2.74 m)
0
12 ft
(3.65 m)
20 ft
(6.096m)
23 ft
(7.01 m)
9 ft
(2.74 m)
12 ft
(3.65 m)
20 ft
(6.096m)
3 ft
(0.91)
15 ft
(4.57 m)
15 ft
(4.57 m)
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
Minor Motion, IR
Major Motion, IR
0
23 ft
(7.01 m)
5 ft
(1.52 m)
0
5 ft
(1.52 m)
32 ft
(9.75 m)
32 ft
(9.75 m)
12 ft
(3.65 m)
16 ft
(4.87 m)
15 ft
(4.57 m)
23 ft
(7.01 m)
15 ft
(4.57 m)
8.5 ft
(2.59 m)
0
12 ft
(3.65 m)
16 ft
(4.87 m)
20 ft
(6.096m)
20 ft
(6.096m)
10 ft
(3 m)
10 ft
(3 m)
3 ft
(0.91)
Recommended Mounting Height: 8 to 12 ft