Product Manual
Table Of Contents
- 1. SQ, SQE introduction
- 2. SQ, SQE applications
- SQ with pressure switch and pressure tank
- Constant-pressure control with CU 301, residential water supply
- Constant-pressure control with CU 301, irrigation
- Maintaining a constant water table
- Emptying or filling a tank
- Pumping from one tank to another
- Setting of operating parameters
- SQE with manual speed control
- 3. Performance range
- 4. SQ, SQE installation
- 5. Sizing and selection
- 6. Cable sizing
- 7. SQ, SQE curve charts
- 8. SQ, SQE technical data
- 9. SQ, SQE construction
- 10. CU331SP variable frequency drive
- 11. Accessories
- 12. SP introduction
- 13. SP product overview
- 14. SP construction
- 15. SP operating conditions
- 16. How to read the curve charts
- 17. SP curve charts and technical data
- 4" and larger wells
- SP 5S (5 gpm)
- SP 7S (7 gpm)
- SP 10S (10 gpm)
- SP 16S (16 gpm)
- SP 25S (25 gpm)
- SP 35S (35 gpm)
- SP 45S (45 gpm)
- SP 62S (62 gpm)
- SP 77S (77 gpm)
- 6" and larger wells
- SP 85S (85 gpm)
- SP 150S (150 gpm)
- SP 230S (230 gpm)
- SP 300S (300 gpm)
- 8" and larger wells
- SP 385S (385 gpm)
- SP 475S (475 gpm)
- 10" and larger wells
- SP 625S (625 gpm)
- SP 800S (800 gpm)
- SP 1100S (1100 gpm)
- 18. SP electrical data
- 19. Accessories
- 20. Energy consumption
- 21. Cables
- 22. Friction loss tables
- 23. Grundfos Product Center
CU331SP variable frequency drive
SQ, SQE, CU 331, and SP
10
50
Motor output (U, V, W)
1)
Output voltage in % of supply voltage.
RS-485 GENIbus connection
The RS-485 circuit is functionally separated from other
central circuits and galvanically separated from the
supply voltage (PELV).
Digital inputs
All digital inputs are galvanically separated from the
supply voltage (PELV) and other high-voltage
terminals.
Signal relays
1)
IEC 60947, parts 4 and 5.
The relay contacts are galvanically separated from
other circuits by reinforced insulation (PELV).
Analog input
1)
The factory setting is voltage signal "U".
All analog inputs are galvanically separated from the
supply voltage (PELV) and other high-voltage
terminals.
Sound pressure level
The sound pressure of the CU331SP is maximum 70
dB(A).
The sound pressure level of a motor controlled by a
Variable frequency drive may be higher than that of a
corresponding motor which is not controlled by a
variable frequency drive.
Output voltage 0-100 %
1)
Output frequency 0-60 Hz
Switching on output Not recommended
Terminal number 68 (A), 69 (B), 61 GND (Y)
Terminal number 18
Voltage level 0-24 VDC
Voltage level, open contact > 19 VDC
Voltage level, closed contact < 14 VDC
Maximum voltage on input 28 VDC
Input resistance, R
i
Approx. 4 kΩ
Relay 01, terminal number 1 (C), 2 (NO), 3 (NC)
Relay 02, terminal number 4 (C), 5 (NO), 6 (NC)
Maximum terminal load (AC-1)
1)
240 VAC, 2 A
Maximum terminal load (AC-15)
1)
240 VAC, 0.2 A
Maximum terminal load (DC-1)
1)
50 VDC, 1 A
Minimum terminal load
24 VDC 10 mA
24 VAC 20 mA
CCommon
NO Normally open
NC Normally closed
Terminal number 54
Current signal A54 = "I"
1)
Current range 0-20, 4-20 mA
Input resistance, R
i
Approx. 200 Ω
Maximum current 30 mA
Maximum fault, terminals 53, 54 0.5 % of full scale