Submittals

FlexFit Multi Series Submittal
Rev. Mar. 2021
CUS
Intertek
36000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM
4U36MS2VHB
When FlexFit series 24k indoor matches with the
4U36MS2VHB, two adapters are required and need to be
purchased separately from Haier parts:
1/4” to 3/8” Part Number: WJ01X23925 (0150704781)
3/8” to 5/8” Part Number: WJ01X23924 (0150707575)
1/2” to 5/8” Part Number: WJ01X23932 (0150709683)
Outdoor Unit
Compressor DC inverter Driven Rotary
Uncrated Dimension (HxWxD)
33 1/8 x 37 3/8 x 13 3/8 in
(840 x 948 x 340 mm)
Crated (HxWxD)
39 5/8 x 42 7/8 x 16 3/8 in
(1005 x 1090 x 415 mm)
Outdoor Sound Rating dB 56
Heat Exchanger Fin Type Blue Fin
Weight (Ship/Net) 191.8/167.6 lbs
Factory Refrigerant Charge R-410A (113.0 oz)
4U36MS2VHB
37 3/8 (948)
33 1/8 (840)
13 3/8 (340)
Cooling Performance
Cooling Capacity Range
(Non-Ducted/Ducted)
5,000~36,000 BTU/
5,000~34,000 BTU
Rated Power Input
(Non-Ducted/Ducted)
3,770/3,590 W
SEER (Non-Ducted/Ducted) 18.0/16.0
EER (Non-Ducted/Ducted) 9.0/8.5
Heating Performance
Heating Capacity Range
(Non-Ducted/Ducted)
6,100~36,500 BTU/
6,100~35,000 BTU
HSPF (Non-Ducted/Ducted) 10.0/9.0
Electrical Requirement
Power Supply 208/230V, 1 Phase, 60 HZ
Operating Voltage Range 187~253 VAC
Recommended Fuse/Breaker Size 30A
MCA 23A
Operating Range
Cooling 14~115°F (-10~46°C)
Heating -4~75°F (-20~24°C)
Pipe Length
Minimum Pipe Length (Each) 6 ft
Maximum Pipe Length (Each/All) 82 ft /230 ft
Pre-Charged 100 ft
Additional Charge 0.2 oz/ft
Maximum Pipe Height Dierence 50 ft
Flare Connection
1/4”, 1/4”, 1/4”, 1/4” (Discharge)
3/8”, 3/8” , 3/8”, 1/2” (Suction)
For more information visit us:
www.Haierductless.com
www.Haierductlesshelp.com
Accessories
Wind Bae
Uses wind bae QAWB40A
Connecting cable to indoor units must be 14/4 AWG unshielded stranded
copper. Cable must be ran continuous, without splicing.
Job Name: __________________________________
Purchaser: __________________________________
Submitted To: _______________________________
Construction: _______________________________
Reference: __________________________________
Approval: ___________________________________
Date: ______________________________________
Submitted By: _______________________________
Unit: _______________________________________
Drawing #: __________________________________
Floor Mounting
Dimensions
7 1/4
(184)
22 7/8
(581)
7 1/4
(184)
15
(381)