Manual

HS-3100/3200 Operator’s Manual
9
2.0 Supplementary Information
2.1 Condition Codes and Zone Numbers
The History and Archive use the following formats for condition codes and zone numbering.
Condition Code
Archive
Alarm List Description
A ALARM Alarm
B bypass Bypass
C com Comlink
D dupl Duplicate Addressable Device
E alert Maintenance Alert
G ground Ground Fault
H Hot Key Pressed
I ilgl Illegal Addressable Device
J Switch
M msng Missing Addressable Device
N nofire Non-Fire/Non-Reporting
P M.PULL Pull Station Alarm
Q abort Releaser Abort
R halt Releaser Halt
S spv Supervisory
T trbl Trouble or Parameter Change
U wrong Wrong Device Type
W WFLOW Waterflow Alarm
A plus sign (+) refers to a new or on condition, a minus sign (-) refers to a restoral or off condition,
and an equal sign (=) refers to a one time event.
Zone Number
PPP:ZZ.SSS Format:
PPP Control Panel Number
ZZ Panel Zone
Panel
Zone
Description
Panel
Zone
Description
0 General Alarm 81 1st Stage Alarm
1 Initiating Circuit 1 82 2nd Stage Alarm
2 Initiating Circuit 2 83 Switch
50 Network Verify 84 Test Mode
51 Comlink 1
85
1
Erase Configuration
52 Comlink 2
86
3
Change Configuration
53 Comlink 3 87 Passcode Tamper
54 Comlink 6
88
1
Database Loaded
60 Output (bell/releaser) Supervision
89
1
Time/Date Change
61 Auxiliary Power Supervision
90
1
Hot Key Activation
64
1
Program Checksum
91
1
Memory Overflow
65
1
Database Checksum
92
1
Network Reboot
66 AC Power
93
1
New Program
67 Low Battery
94
1
Network Reboot Required who
69
1
Program Restart
95
1
Network Reboot Required why
80
2
Privilege Level