Manual

HS-3100/3200 Operator’s Manual
12
BBBBBBAA
1234567812
List the status of the 8 bell circuits and the 2 auxiliary power circuits.
Each column represents one circuit. A dot (.) indicates a normal
condition, an S indicates a short, an O indicates an open and a G
indicates a ground. Auxiliary power circuits are not supervised for
opens. A bell that has been installed with the polarity the wrong way
may appear as a short on the bell circuit. Note: This message will
always be shown if the panel is in Test Mode. Bells 3-8 indicates status
on the optional NAC expansion modules.
Network module not
installed
The HS32NTWR Network Board has not been installed. The network
cannot be used unless this board is installed.
port 1 panel ?
off line
This Control or Annunciator Unit is not reporting in over network port 1.
This message will be repeated for each panel that is off line.
port 2 off line The network communications on port 2 have stopped.
port 3 off line The communications on port 3 have stopped.
wrong port 3 program The port 3 selections in the NP database do not match the firmware
option. Either correct the database or load the correct firmware.
BBBBBBBBFFFF
123456781234ASTWGL
The current status of the relays in the system. Each column represents
one relay. A dot (.) will appear under each relay that is off and an
asterisk (*) will appear under each relay that is currently switched on.
Note: This message appears in Test Mode only.
B Bell Circuit 1 to 8 T Trouble Relay
F Function Relay 1 to 4 W Walk Test Relay
A Alarm Relay G Ground Fault Relay
S Supervisory Relay L LCD Back Light Relay
passcode tamper There have been 3 consecutive attempts to enter an invalid passcode.
watchdog disabled The watchdog causes the panel to be reset if it fails to operate correctly.
If the watchdog is disabled, the panel will not automatically reboot if it
fails to operate correctly.
NETWORK REBOOT
required
There has been a loss of communications on the network resulting in
lost frames. The panel ID listed is the panel that detected the problem.
This trouble will be sent to all other panels and annunciators on the
network. Select PROGRAM/PORTS/NETWORK/REBOOT from the
LCD menu to send the reboot command to all panels.
time not set The time has not been set since the panel has been Rebooted. The time
displayed on the clock may be wrong. Enter the correct time.
illegal addressable
devices
There are addressable devices connected to the panel that are not
included in the downloaded database.
network verify ?
missing
The Network Verify feature has detected that the panel listed is not
reporting in. This is indicative of a communications error.
Message Description