network verify ?
illegal
The Network Verify feature has detected that the panel listed is not this
panel’s database. Update the database in this panel. Remember that it
is recommended that all panels be downloaded with the same database
for correct operation.
network verify ?
version
The Network Verify feature has detected that the panel listed is running
a different version of operating program and database. Update all
panels in the network to use the same operating program and database.
addressable devices
bypassed
One or more addressable devices have been bypassed. To view which
devices have been bypassed, select PROGRAM/ADDRESSABLE/
BYPASS/OFF from the LCD menu.
manual control
modules
One or more control modules have been forced either on or off. To view
which control modules are forced, select PROGRAM/ADDRESSABLE/
CONTROL MODULES/OFF from the LCD menu.
manual function
relays
One or more general function relays have been forced either on or off.
To view which relays are forced, select PROGRAM/RELAYS/MODES/
INDIVIDUAL from the LCD menu.
manual switches One or more switches with timers have been forced either on or off. This
is not shown for switches that do not have timers. To view which
switches are forced, select PROGRAM/SWITCHES/INDIVIDUAL from
the LCD menu.
MEMORY OVERFLOW An event happened that caused an out of memory condition. This
means that an event has been lost by the panel. The printer and Port 3
will discard frames to help relieve the memory problem. The panel will
have to have a Hard reboot done.
memory lockout The extended memory lockout has timed out. The panel will need a
Hard Reboot to correct this problem. Please notify Harrington of the
occurrence of this error. Include in your report the panel serial number
and the name, date and time of the operating program.
not enough ram The operating program requires more extend RAM then the panel
actually has. Certain addressable functions and/or the alarm list may not
work. Basic fire detection will continue to operate. Upgrade the RAM in
the panel to clear this trouble. This should only appear when upgrading
the operating program of panels that have been in the field for a number
of years.
Message Description