HSI #780-0867 FireSpy Tracker Installation Manual
13
Table 2-19: City tie/reverse polarity communicator (UCT) specifications.
Parameter Rating
Supply voltage 24V*
Input current draw 350mA max
Relay contacts
Trouble contacts
Alarm contacts
1A @ 28VDC, form C
5A @ 28VDC, form C
Remote station transmitter circuit outputs (power limited)**
Voltage
Current
16.5 – 24.6VDC
14mA max
Local energy city tie outputs (not power limited)
Standby voltage
Standby current
Alarm voltage
Alarm current
Ripple voltage (alarm)
Intended trip coil
18-40mVDC
1.5mA max
16-28VDC
270mA max (momentary load)
1.2V max
14.5 ohm
* The same power source must be used for powering the UCT and relay contact wiring.
** These circuits are to be supervised by the remote station.
2.3.13 Enclosures
Table 2-20: Enclosure dimensions and module mounting provisions.
T1-CAB
T8000-CAB
T2000-CAB
T2000E-CAB T8000-EXP
Size (inches)
Overall
Backbox
W x H x D
15.88 x 25.19 x 4.8
14.5 x 23.5 x 4
W x H x D
15.88 x 25.19 x 4.8
14.5 x 23.5 x 4
W x H x D
19.25 x 33.25 x 4.5
18 x 32 x 4
W x H x D
11.37 x 15.44 x 3.8
10 x 14 x 3
Knockouts
(1-1/8 dia)
4 top
3 each side
4 top
3 each side
3 top, 2 bottom,
4 each side
3 top
3 bottom
Module Quantity of modules that may be mounted
T1-MB 1
T8000-MBC or
T2000-MBCLC or
1 1
T8000-LCU 2* 2*
T8000-CM 2* 2*
T8000-SRM 1* 1*
T8000-RC 2
T-UDACT 1
T8000-NCA 1
25HAVE, 50HAVE,
or 100HAVE
1
ZSC-2A or ZSC-4B 2*
Batteries (2) 12V, up to 12Ah** (2) 12V, up to 12Ah** (4) 12V, up to 18Ah†
* A total of two mounting locations are provided for a combination of these modules.
** Larger batteries may be mounted in an auxiliary UL864 Listed enclosure.
Two batteries are for the fire system and two batteries are for the audio system. 100HAVE may use up to 24Ah batteries.