HSI #780-0867 FireSpy Tracker Installation Manual
13
Table 2-19: City tie/reverse polarity communicator (UCT) specifications.
Parameter Rating
Supply voltage 24V*
Input current draw 350mA max
Relay contacts
Trouble contacts
Alarm contacts
1A @ 28VDC, form C
5A @ 28VDC, form C
Remote station transmitter circuit outputs (power limited)**
Voltage
Current
16.5 – 24.6VDC
14mA max
Local energy city tie outputs (not power limited)
Standby voltage
Standby current
Alarm voltage
Alarm current
Ripple voltage (alarm)
Intended trip coil
18-40mVDC
1.5mA max
16-28VDC
270mA max (momentary load)
1.2V max
14.5 ohm
* The same power source must be used for powering the UCT and relay contact wiring.
** These circuits are to be supervised by the remote station.
2.3.13 Enclosures
Table 2-20: Enclosure dimensions and module mounting provisions.
T1-CAB
T8000-CAB
T2000-CAB
T2000E-CAB T8000-EXP
Size (inches)
Overall
Backbox
W x H x D
15.88 x 25.19 x 4.8
14.5 x 23.5 x 4
W x H x D
15.88 x 25.19 x 4.8
14.5 x 23.5 x 4
W x H x D
19.25 x 33.25 x 4.5
18 x 32 x 4
W x H x D
11.37 x 15.44 x 3.8
10 x 14 x 3
Knockouts
(1-1/8 dia)
4 top
3 each side
4 top
3 each side
3 top, 2 bottom,
4 each side
3 top
3 bottom
Module Quantity of modules that may be mounted
T1-MB 1
T8000-MBC or
T2000-MBCLC or
1 1
T8000-LCU 2* 2*
T8000-CM 2* 2*
T8000-SRM 1* 1*
T8000-RC 2
T-UDACT 1
T8000-NCA 1
25HAVE, 50HAVE,
or 100HAVE
1
ZSC-2A or ZSC-4B 2*
Batteries (2) 12V, up to 12Ah** (2) 12V, up to 12Ah** (4) 12V, up to 18Ah†
* A total of two mounting locations are provided for a combination of these modules.
** Larger batteries may be mounted in an auxiliary UL864 Listed enclosure.
† Two batteries are for the fire system and two batteries are for the audio system. 100HAVE may use up to 24Ah batteries.