HSI #780-0867 FireSpy Tracker Installation Manual
21
LINE INPUT
120VAC - 50/60Hz
230VAC - 50/60Hz
RS485
TO SERIAL
MODULES
A+A- B+B-+- - +
24VDC
P8
RS485
B+A+ A-B- B+A+ A-B-
P7 NAC
B+
A+ A-B-
P8 NAC
NC
COM
NO
NC
COM
NO
NC
COM
NO
P9 NACP6
J3
P3
P4
P5
NAC
SUPV ALARMTROUBLE ALARM
A+A- B+B-
P9
SLC2SLC1
MBC-LC
TYPICAL
STYLE Y
(CLASS B)
WIRING
10K
LINE
NEU/LINE
EARTH
TYPICAL STYLE Z
(CLASS A)
WIRING
(end-of-line resistor
not needed)
CONTACTS RATED
10A @ 30VDC
10A @ 250VAC
1.0 POWER FACTOR
USE ONLY POLARIZED
DEVICES ON NACs
Polarity shown is alarm condition
ALL NACs ARE REGULATED 24 DC
SERIAL
PORT
24VDC
TO SERIAL
MODULES
BATTERY
CABLE
(TO P2)
+
+
+
+
10K10K
B+A+ A-B-
J6
TO NETWORK
COMMUNICATOR
USB
PORT
ETHERNET
PORT
(OPTIONAL)
290-0119
TYPICAL
STYLE B (CLASS B)
WIRING
4.7k 4.7k
A+A- B+B-
ZONE
TYPICAL
STYLE D (CLASS A)
WIRING
A+A- B+B-
P10
ALL NACs ARE REGULATED 24 DC
NOTES:
1) Use only smoke detectors that are listed in compatibility listing in
owner's manual.
2) Leave end-of-line resistors on unused circuits.
3) All terminals are rated for 14-22 AWG wire unless otherwise noted.
4) Combined load of all devices, including indicating appliances, is not to
exceed 7A.
J1 jumpers present
TYPICAL STYLE 4 (CLASS B) WIRING
SLC B-
SLC B+
Example SLC wiring on MBC-LC
Isolators (optional) separate each zone
TYPICAL STYLE 6 (CLASS A) WIRING
ZONE 1
SLC A-
SLC A+
SLC B-
SLC B+
SLC A-
SLC A+
SLC B-
SLC B+
ZONE 2
Isolators separate each detector
Remove J1 jumpers
Remove J1 jumpers
TYPICAL STYLE 7 (CLASS A) WIRING
A+A- B+B-
ZONE
S
P
P
P
TO RC
Marks non-supervised circuits
Marks non-power-limited circuits
All others are supervised and power limited.
Segregate power-limited wiring from
non-power-limited wiring by at least 1/4 inch.
SUPERVISED AND POWER LIMITED
S
P
4.7k
4.7k
Example zone wiring on CM
J1
SW2
8
1
(RESERVED)
SW1
8
1
(RESERVED)
SW4
8
1
(RESERVED)
SW3
8
1
ON/OFF
Figure 3-3: Wiring on MBC-LC