User Manual

D
C
B
HSI #780-0867 FireSpy Tracker Installation Manual
29
Appendix B. Compatible Devices
B.1 Startup delay for devices with alarm verification
The Tracker system includes an alarm verification feature that will result in a delay of the system alarm
signal from the indicated circuits.
The following statement applies to installations intended to meet UL864 requirements: The total delay
(control unit plus smoke detector) shall not exceed 60 seconds. No other smoke detector shall be
connected to these circuits unless approved by the local authority having jurisdiction.
The following statement applies to installations intended to meet California State Fire Marshal
requirements: For fire alarm verification feature (delay of fire alarm), the maximum retard/reset/restart
period (control unit plus detector) must be adjusted to 30 seconds or less.
For the devices below, the delay start-up time marked on the installation wiring diagram of the smoke
detector or on the installed smoke detector is to be used.
Circuits Compatible smoke detectors with alarm verification
LCU and MCCLC, Class A and B Apollo 55000-550, -650, -886
Harrington TS8-DP, TS8-DH, TS8-DM
B.2 Addressable SLC devices (for use with T8000-LCU, T2000-MBCLC, and
T1-MB)
Each SLC circuit must use devices from a single series of compatible devices. Do not mix and match
unless otherwise noted. For example, do not use System Sensor and Apollo devices on the same circuit.
The following devices below may be used together on the same SLC circuit:
Harrington ISpy, TSpy, HSPS
Apollo XP95, Discovery
Air Products
B.2.1. System Sensor
Harrington
Part No.
System Sensor Model Description
Detectors
349-0508 1551 Ion smoke detector
349-0494 2551 Photo smoke detector
349-0495 5551 Heat detector, fixed temperature
349-0646 5551R Heat detector, rate-of-rise
349-1048 1251B Ion smoke detector – low profile
349-1046 2251, 2251B Photo smoke detector – low profile
349-1056 2251BR Photo smoke detector to be used with DNR/DNRW duct smoke detector
349-1047 2251TB Photo/thermal multicriteria detector (Acclimate)
349-1071 2251TMB Photo/thermal multicriteria detector (Acclimate)
349-1049 5251B Fixed temperature heat detector, 135°
349-1059 5251H Fixed temperature heat detector, 190°