Power Supply User Manual

Chapter 9: 6801PS-48 Power Supply Module Installing the 6801PS-48
40 6800/7000 Series - Frames and Power Supplies Installation and Operation Manual
Installing the 6801PS-48
Precautions
To reduce the risk of electric shock or energy hazards, heed the following
cautions:
Connect the 6801PS-48 to a reliably grounded SELV source or a
centralized DC source.
The branch circuit overcurrent protection must be rated a
maximum 10 A circuit breaker in series with a maximum 5 A
listed fuse. (
See suggested protection devices on page 41.)
Use 14 AWG solid copper conductors only.
A readily accessible disconnect device that is suitably approved
and rated, shall be incorporated into the field wiring. (See
suggested breaker switch type on page 41.)
To be installed in a restricted access area in accordance with the
NEC or the authority having jurisdiction.
To reduce the risk of electric shock, heed these cautions:
Perform installation and exchange only if you are a trained
technician who is familiar with these instructions and aware of
the shock hazards of working with live equipment.
Install the 6801PS-48 power supply in accordance with the
schematic diagram shown on page 41.
Power can only be disconnected completely from the 6800/7000
series frame through a studio installed breaker or fuse.