BURNER INSPECTION AND CLEANING:
With the heater “ON”, remove the front
access panel and make a visual inspection of
the main burners through the sight glass (see
Figure 25.) The main burner ames should be
about ½” to 2” in height and should not “lift”
off the burner ports (see Figure 29).
A normal ame is blue, without yellow
tips. Yellow tips or a totally yellow or “lazy”
ame may be an indication of a fuel-rich mix-
ture due to restricted air supply. Spider nests in
the burner and/or gas orices may also cause
yellow tips.
Figure 29: Burner Flame characteristics
EXTERNAL HEAT EXCHANGER INSPECTION AND CLEANING:
Remove the louvered exhaust cover panel (see Figure 12) and inspect the external surfaces of the heat exchang-
er for soot accumulation. If soot has accumulated, it must be removed by following the recommended procedure:
1. Turn pump, main gas valve, and heater power “OFF”.
2. Remove heat exchanger according to the procedure in Section II, under “Reversible Water Connections”.
WARNING: BURN HAZARD Do not use a wire brush to remove soot from the
heat exchanger. This could cause a spark and ignite the gases trapped within the soot.
3. Using a soft-tipped brush such as a paint brush, apply a degreaser to the entire heat ex-
changer surface (top and bottom). Allow the heat exchanger to sit for a period of time to
allow the degreaser to loosen the soot. Wash the heat exchanger using a garden hose ensuring
both the top and bottom surfaces are cleaned. Re-assemble the heater by reversing the disassembly steps.
Although the heat exchanger should be cleaned of soot and reinstalled, the fact that sooting occurred
should be investigated, as it may indicate other problems such as:
Insufcient air supply
Inadequate venting
High or low gas pressure
Blockage of burner tubes or orices
Blockage of blower inlet
Low voltage supply causing blower to “spin” slower
Improper heater location installation
Incorrect gas supply pipe size
Excessive water ow through heat exchanger
LP tank below 30% full