- WattMaster Water Source Heat Pump Operations Manual

Section 3 WattMaster WHP
3-8 Programming
View Alarms
Alarm Address Locations
Alarm Clearing
The System Manager can be programmed to poll all the
units on your heat pump system for alarm information. This
allows the centrally located System Manager to display an
Alarm Indicator whenever an alarm condition exists
anywhere on your system. The actual alarms are not
displayed on this screen, only the Unit ID where the alarm
is located. The example screen shows that a unit at location
118 has experienced an alarm condition. This alarm may or
may not be current, as the System Manager latches the
condition. This makes it possible to determine if any
intermittent alarm conditions have occured. To find out
what the alarm is, if it is still current, access the status
screens for the Unit IDs that are displayed on the SYSTEM
ALARM STATUS screens.
If all the alarm conditions have been corrected at the
individual units, you can clear these alarms from the
System Manager on the following screen. Use the
Left/Right arrow keys to select the YES/NO response
desired. If you clear the alarms, but some still exist, the
System Manager will show an alarm indication, when the
affected unit is polled again.