- WattMaster Water Source Heat Pump Operations Manual

WattMaster WHP Section 4
Start-Up and Troubleshooting 4-5
2.2 Becoming Familiar with the WHP
Controller
E
W
D
O
G
0-5
VDC
0-1
VDC
DIAGNOSTIC BLINK
CODE LED
ADDRESS SWITCH
( ADDRESS 18 SHOWN )
EPROM
PIN 1
INDICATION
RAM
RAM SIZE
SELECT JUMPER
PAL
REAL TIME
CLOCK CHIP
24VAC
POWER
INPUT
POWER LED
COMMUNICATIONS
DRIVER CHIP
COMMUNICATIONS
LED
ANALOG INPUTS
STATIC PRESSURE
SENSOR INPUT
RS-485
COMMUNICATIONS
LOOP
CPU
Space Sensor
Slide Adjust
Supply Air Temp
Leaving Water
Temp or
Dirty Filter
Lockout
24 VAC Common for Inputs 1 - 3
Compressor-On/Off (Heat 2)
Heat Pump Reset (Cool 1)
Aux. Heating or Cooling (Cool 2)
Rev. Valve-On/Off (Heat 1)
Fan-On/Off
24 VAC Common for Inputs 1 - 3
Mounting Backplate
WHP Controller Component Layout
2.2.1 24 VAC Power Connector
This connector provides power to the WHP Controller.
24VAC - The “hot” side of the control transformer.
GND - The grounded side of the control transformer. If the secondary of the con-
trol transformer is not grounded, you must still observe polarity if the trans-
former powers any other device!
Warning: Connect only the GND terminal to the grounded side of a transformer
- Failure to properly observe polarity will result in
damage to the system. Observe polarity at all points in the
system.