2
Installation Directions
Prepare Strike
5. Choose the appropriate faceplate for the strike as
illustrated in Diagram 5 on page 3.
6. Connect wires from the power source to the strike.
7. Install the electric strike unit in jamb cutout, using
#12-24 x 1/2” Mounting Screws provided.
8. If horizontal adjustment is needed, see Diagram 6
on page 3.
CAUTION! Before connecting any device at the installation site, verify input voltage using a multimeter.
Many power supplies and low voltage transformers operate at higher levels than listed. Any input voltage exceeding
10% of the solenoid rating may cause severe damage to the unit and will void the warranty.
Finish Installing
3
Installation Diagrams
LBM WIRING
White
Orange Normally Open
Green
Normally Closed
Common
LBSM WIRING
Brown
Blue Normally Open
Yellow
Normally Closed
Common
DIAGRAM 3: STRIKE MONITORDIAGRAM 2: LATCHBOLT MONITOR
Convert Mode
d. Verify the strike is now in the Fail Safe operation
mode. If the strike still operates as Fail Secure, be
sure screws are fully seated in the top position.
Verify
DIAGRAM 4: FAIL SAFE CONVERSION*
DIAGRAM 6: HORIZONTAL ADJUSTMENT
If horizontal adjustment is needed, 1 or 2
keeper shims can be added as illustrated below.
If adding a single shim use the
#4-40 x 1/8” Keeper Shim
Screws.
If adding both shims use the
#4-40 x 3/16” Keeper Shim
Screws.
One Shim
Both Shims
DIAGRAM 5: FACEPLATE OPTIONS
b. A Non-Handed center-lined faceplate is provided for
use with cylindrical locksets
a. A Non-Handed oset faceplate is provided for use
with mortise locksets. The mortise lock deadlatch
should be depressed by the faceplate when the
door is closed.
*USING THE 4500 FOR FAIL SAFE OPERATION NEGATES FIRE RATING
DIAGRAM 1: 12V to 24V CONVERSION
RED
RED/GREEN
BLACK
VIOLET
RED
BLACK
VIOLET
RED/GREEN
IF CONNECTOR IS MISSING
(+ 12 VDC)
(-NEG)
(+ 24 VDC)
(-NEG)
ELECTRIC
STRIKE
ELECTRIC
STRIKE
CONNECT
TOGETHER
CONNECT
TOGETHER
CONNECT
TOGETHER
Prepare Frame
4. Prepare frame using appropriate template for your
lockset on page 4. Schlage L9000 & Yale 8700 locksets
must use the template labeled “Schlage L9000 & Yale
8700 Locks Only. All other locksets should use the
template labeled “CYLINDRICAL LOCKSET or “MORTISE
LOCKSET.
1. Select the appropriate Plug In Connector that matches
system power and electrically connect as illustrated in
Diagram 1. For 12V AC/DC or 16V AC, the pigtail marked
“12 VDC should be used. For 24V AC/DC, the pigtail
marked “24 VDC should be used.
2. If using Latchbolt Monitor (LBM) or Latchbolt Strike
Monitor (LBSM), see Diagram 2 & 3 on page 3 to com-
plete wiring. State of switch is listed for an unpowered
strike and LBM in unactuated (door open) position.
3. Verify that the strike is in the correct mode of
operation. This unit ships in Fail Secure mode. If you
need to convert to Fail Safe see Diagram 4 on page 3.
NOTE: FAIL SAFE CONVERSION NEGATES FIRE RATING.
aa
b
White
Orange
Green
Brown
Blue
Yellow
Fire Door
Safety Screw
Unpowered and in
unactuated state
Unpowered and in
unactuated state
a. Remove the Fire Door Safety Screw as illustrated.
b. Loosen the two #2-56 screws located on the back of
the strike as shown above, but do not remove them.
c. Move screws from the bottom of the hole (fail
secure position) to the top hole (fail safe position) and
re-tighten.