S-BT Threaded Fastener Specification

Table Of Contents
page 20 Specifications
2.8.1 Functional bonding and terminal connection in a circuit
Forpermanentcurrent(leakagecurrent)duetostaticchargebuiltupinpipesor
whenclosinganelectricalcircuit.
Single point connection:
Recommended electrical
connectors:
Maximumallowable
permanentcurrent:
Connection
conguration:
TypeAconnection:
S-BT-ERM10/15SN6
S-BT-ERW10/15SN6
S-BT-EFM10/15AN6
S-BT-EFW10/15AN6
S-BT-ERM8/15SN6
S-BT-EFM8/15AN6
I
th
=57A
TypeBconnection:
S-BT-ERM10HC120
S-BT-ERW10HCAWG4/0
S-BT-EFM10HC120
S-BT-EFW10HCAWG4/0
I
th
=269A
Note:
•Recommendedmaximalcrosssectionofconnectedcableaccording
IEC60947-7-2andIEC60947-7-1:
10mm²(8AWG)copper(testedpermanentcurrentI
th
=57A)
120mm²(4/0AWG)copper(testedpermanentcurrentI
th
=269A)
•Fasteningofthickercableisacceptable,ifthemaximumallowablepermanent
currentI
th
isnotexceededandtheprovisionsoncablelugthicknesst
cl
are
observed.